HP rp3440 Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440
HP rp3440 Manual
View all HP rp3440 manuals
Add to My Manuals
Save this manual to your list of manuals |
HP rp3440 manual content summary:
- HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 1
HP 9000 rp3410 and HP 9000 rp3440 Site Preparation Guide HP 9000 rp3410 and HP 9000 rp3440 Manufacturing Part Number: A7137-96005 Fifth Edition April 2005 U.S.A. © Copyright 2004-2005 Hewlett-Packard Development Company, L.P.. - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 2
to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 3
Weights 13 Component Dimensions 13 Grounding 14 Electrical Specifications 15 AC Power Cords 15 Circuit Breaker 15 AC Power Specifications 15 Power Consumption and Cooling 16 Environmental Specifications Delivery Survey 41 Information to Collect Before You Contact Support 44 Glossary 45 3 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 4
Contents Index 47 4 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 5
Figures Figure 1-1. HP 9000 rp3410 and HP 9000 rp3440 Server 11 Figure 2-1. Raised Floor Metal Strip Ground System 24 Figure 2-2. Delivery Survey (Part 1 42 Figure 2-3. Delivery Survey (Part 2 43 5 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 6
Figures 6 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 7
support information for authorized service providers, customer system administrators, and HP support • Text to be replaced with text that you supply is represented using this font. Example: "Enter buttons, tabs, and menu items) are represented using this font. Examples: The Control key, the OK button - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 8
diagnostics and event monitoring tools, is at the http://docs.hp.com/hpux/diag/ Web site. This site has manuals, tutorials, FAQs, and other reference material. Web Site for HP Technical Support: http://us-support2.external.hp.com HP's IT resource center Web site at http://us-support2.external - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 9
.html • HP-UX Virtual Partitions http://www.hp.com/hpbooks/prentice/ptr_0130352128.html HP Books are available worldwide through bookstores, online booksellers, and office and computer stores. Printing History The Printing History below identifies the edition dates of this manual. Updates are - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 10
10 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 11
for the HP 9000 rp3410 and HP 9000 rp3440 server. Table 1-1 Hardware Specifications Component Microprocessors Memory HDDs rp3410 rp3440 One dual processor module with one or two PA RISC processors enabled. Each processor is 800 MHz/1.5 MB cache with 32 MB or 64 MB L2 cache Supports up to - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 12
Hardware Specifications (Continued) Component SCSI LAN PCI slots Core I/O DVD-ROM External storage Power supply rp3410 rp3440 Integrated port, four USB 2.0 ports, integrated RJ-45 LAN on iLO manageability card None Optional One 650W power supply. You can install a second power supply to provide - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 13
System Specifications Dimensions and Weights Dimensions and Weights This section provides dimensions and weights of HP 9000 rp3410 and HP 9000 rp3440 server components. Component Dimensions Table 1-2 Server Component Dimensions Dimension Rack dimensions (depth x width x height) Value 67.9 cm ( - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 14
System Specifications Grounding Grounding The site building shall provide a safety ground or protective earth for each AC service entrance to all cabinets. Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the branch-circuit supply - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 15
System Specifications Electrical Specifications Electrical Specifications This section provides electrical specifications for your HP server. AC Power Cords Table 1-3 lists the various power cables available for use with the HP 9000 rp3410 and HP 9000 rp3440 servers. Table 1-3 Power Cords Part - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 16
or use a power block with a switch. Power Consumption and Cooling Power consumption for a typical server is 600W/2050 Btu/h. The power consumptions listed in the following table are valid for a standard configuration as shipped (one 1 GHz processor, 6 GB of memory, 650W power supply, three hard - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 17
System Specifications Electrical Specifications Table 1-5 Additional Component Power Consumption (Continued) Additional Component SCSI hard disk (idle) PCI card 16W 10W to 25W Power Consumption 54.5 Btu/h 34.12 Btu/h to 85.30 Btu/h Chapter 1 17 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 18
specifications for the HP server problems and cause excessive wear of the disk surface. Table 1-6 Environmental Specifications emission (ISO 7779) Sound power levela Tower system Typical One processor enabled, one or two SCSI hard disk drives and less than 8 GB of memory. c. Two dual processors, - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 19
) and should make the final decision regarding adherence to region-specific or area-specific electrical codes and guidelines. Proper design and installation of a power distribution system for a HP 9000 rp3410 or HP 9000 rp3440 server requires specialized skills. Those responsible for this task must - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 20
connectors to 80% of their RMS current ratings Power Quality The HP 9000 rp3410 and HP 9000 rp3440 servers are designed to operate over a wide range of voltages and frequencies. The server is tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 21
conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for HP computer equipment: • Dedicated power source-Isolates a HP 9000 rp3410 or HP 9000 rp3440 server power distribution system from other - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 22
HP 9000 rp3410 or HP 9000 rp3440 server requires two methods of grounding: • Power distribution safety grounding • High frequency intercabinet grounding Power Distribution Safety Grounding (LAHJ) The power steel, or a conductive type cold water service pipe provide an earth ground. Electrical Conduit - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 23
supplied). When connecting this ground, ensure that the raised floor is properly grounded for high frequency. Power cabinet and electrical service entrance ground at absolute safety minimum. HP recommends the following approaches to four strips using 1/4 in. (6.0 mm) bolts - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 24
a ground grid with bolted down stringers and corrosion resistive plating (to provide low resistance and attachment points for connection to service entrance ground and HP computer equipment). The use of conductive floor tiles with this style of grid further enhances ground performance. The structure - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 25
3. Check that the braid contact on each end of the ground strap consists of a terminal and HP equipment. Refer to the appropriate installation guide a high impedance that causes serious problems, such as erratic equipment operation. Data Communications Cables Power transformers create high-energy - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 26
(ESD) prevention • Acoustics (noise reduction) Computer Room Preparation The following guidelines are recommended when preparing a computer room for a HP 9000 rp3410 or HP 9000 rp3440 server: • Locate the computer room away from the exterior walls of the building to avoid the heat gain from windows - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 27
be zoned to deliver an adequate amount of supply air to the cooling air intake vents of the HP 9000 rp3410 and HP 9000 rp3440 server equipment cabinets. Supply air temperature should be maintained within the following parameters: • Ceiling supply system-From 55°F (12.8°C) to 60°F (15.6°C) • Floor - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 28
HP 9000 rp3410 and HP 9000 rp3440 server cabinets. The supply air is then available near the cooling air intake vents of the HP 9000 rp3410 and HP 9000 rp3440 server . ESD can cause component damage during servicing operations. Paper feed problems on high-speed printers are usually encountered - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 29
Elements Specifically, disk up on the boards. Other failures to power supplies and other electronic components can be caused of some raised floor tiles. Although this problem is relatively rare, it may be an intermittent failures on your electronic equipment, HP strongly recommends that your site be - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 30
General Site Preparation Guidelines Environmental Elements Electrostatic Discharge (ESD) Prevention Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a static charge is determined by the following factors: • Types of materials • Relative - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 31
must be able to support the total weight of the installed HP 9000 rp3410 and HP 9000 rp3440 server as well as the weight of the individual cabinets HP 9000 rp3410 or HP 9000 rp3440 server installation. Raised Floor Loading Raised floor loading is a function of the manufacturer's load specification - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 32
panel can support (without failure) when a wheel of specified diameter and width is rolled across the panel Computed by dividing total equipment weight by the for the installation of a HP 9000 rp3410 or HP 9000 rp3440 server. Based on specific information provided by HP, Tate Access Floors has - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 33
Guidelines Facility Characteristics Table 2-3 Typical Raised Floor Specifications (Continued) Itema Rating Ultimate load 4,000 lb computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 34
affect servicing operations. HP 9000 rp3410 and HP 9000 rp3440 server cabinets, larger space requirements are needed to keep ambient air intake to the HP 9000 rp3410 and HP 9000 rp3440 server power cables • Access to air conditioning ducts, filters, lighting, and electrical power hardware • Power - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 35
• Equipment cable routing General Site Preparation Guidelines Space Requirements Chapter 2 35 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 36
Formulas The conversion factors provided here are intended to ease data calculation for systems that do not conform specifically to the configurations listed in this Site Preparation Guide. Listed below are the conversion factors used in this document, as well as additional conversion factors which - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 37
mailed to HP (if required to be an HP task) • 30 days before installation - Primary power and air HP site preparation specialist to resolve any last minute problems NOTE Not all installations follow a schedule like the one noted above. Sometimes, a HP 9000 rp3410 or HP 9000 rp3440 server - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 38
Checklist Sample Site Inspection Checklist The following table lists the type of information needed in a site inspection. Table 2-4 Customer and HP Information Customer Information Name: Street Address: State or Province: Zip or postal code: Primary customer contact: Secondary customer contact - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 39
Is there a remote console telephone line available with an RJ11 jack? 9. Is a telephone line available? 10. Are customer supplied peripheral cables and LAN servicing needs? (for example, vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power used - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 40
Checklist Table 2-5 Site Inspection Checklist (Continued) Please check either Yes or No. If No, include comment# or date 26. Are there any equipment servicing hazards (loose ground wires, poor lighting, and so on)? Cooling No. Area or condition Yes No 27. Can cooling be maintained between 20 - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 41
or recommendations form, see Figure 3-2. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size and weight limitations • Special delivery procedures • Special equipment required for installation, such as tracking or hoists - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 42
General Site Preparation Guidelines Delivery Survey Figure 2-2 Delivery Survey (Part 1) DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes No ___________ Circle the location of the dock and give street name if different than address. North West East South - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 43
General Site Preparation Guidelines Delivery Survey Figure 2-3 Delivery Survey (Part 2) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb or kg Depth Height Width Dept Height Widt STAIRS Please list number of flights and stairway - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 44
Support Before you contact HP support, you should: Step 1. Check information on troubleshooting and attempt to solve the problem. Refer to "Troubleshooting" in the Operation Guide for your system, available at http://docs.hp server (for example: rp3410 or rp3440) • The product number of your server. - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 45
heat transfer rate. C CompactPCI The newest specification for PCI-based industrial computers is called CompactPCI current The peak current flowing into a power supply the instant AC power is applied. This peak is usually Commission) regulates a portion of this problem through Part 15 of their rules - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 46
specification. Power factor The ratio of true power to apparent power in an AC circuit. In power conversion technology, power factor is used in conjunction with describing the AC input current to the power supply customer will experience this level of power consumption. Tonnage The unit of measure - HP rp3440 | Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 47
, 26 D data communications cables, 25 dimensions and weights, 13 ducts, air conditioning, 28 E electrical and power distribution safety grounding, 22 power panel grounds, 22 power quality, 20 sources of electrical disturbances, 21 system installation guidelines, 25 electrical specifications
HP 9000 rp3410 and HP 9000 rp3440
Site Preparation Guide
HP 9000 rp3410 and HP 9000 rp3440
Manufacturing Part Number: A7137-96005
Fifth Edition
April 2005
U.S.A.
© Copyright 2004-2005 Hewlett-Packard Development Company, L.P..