HP rp3440 Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 16

Power Consumption and Cooling, Table 1-4, System Power Specifications - memory configuration

Page 16 highlights

System Specifications Electrical Specifications Maximum input current is the worst case or highest current given the lowest input voltage and the maximum input power. Table 1-4 System Power Specifications Parameter Input voltage Input current (max) Input frequency Measured input power Available power (output) Max current at +12V Max current at -12V Max current at +3.3V Max current at +5V Max current at +3.3V standby Total Rating Peak (15 sec) 100 - 240 VAC 7.2A at 115 VAC or 3.6A at 220 VAC 50 to 60 Hz 560W 650W 49A 0.35A 34A 18A 3.5A Off Off Off Off Off 0.5A Off Off 31A Off Max. per PCI-X Sockets 64-bit, 133 MHz Off Off Off Off 85W total for PCI sockets Off 0.1A 4.6A 3A Off If an overload triggers the power supply overload protection, the system is immediately powered off. To reset the power supply unit perform the following steps: 1. Disconnect the power cord. 2. Determine what caused the overload by contacting a HP support representative. 3. Reconnect the power cord, then reboot the system. If an overload occurs twice, there is an undetected short circuit somewhere. When you use the front panel's power button to turn off the workstation, power consumption falls below the low power consumption, but doesn't reach zero. To reach zero power consumption in "off " mode, either unplug the workstation or use a power block with a switch. Power Consumption and Cooling Power consumption for a typical server is 600W/2050 Btu/h. The power consumptions listed in the following table are valid for a standard configuration as shipped (one 1 GHz processor, 6 GB of memory, 650W power supply, three hard disk drives, one graphics card, one LVD SCSI card). All information in this section is based on primary power consumptions. Table 1-5 Additional Component Power Consumption Additional Component Processor SCSI hard disk drive (with I/O access) 130W 23W Power Consumption 443.6 Btu/h 78.4 Btu/h 16 Chapter 1

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

System Specifications
Electrical Specifications
Chapter 1
16
Maximum input current is the worst case or highest current given the lowest input voltage and the maximum
input power.
If an overload triggers the power supply overload protection, the system is immediately powered off. To reset
the power supply unit perform the following steps:
1. Disconnect the power cord.
2. Determine what caused the overload by contacting a HP support representative.
3. Reconnect the power cord, then reboot the system.
If an overload occurs twice, there is an undetected short circuit somewhere.
When you use the front panel’s power button to turn off the workstation, power consumption falls below the
low power consumption, but doesn’t reach zero. To reach zero power consumption in “off” mode, either unplug
the workstation or use a power block with a switch.
Power Consumption and Cooling
Power consumption for a typical server is 600W/2050 Btu/h. The power consumptions listed in the following
table are valid for a standard configuration as shipped (one 1 GHz processor, 6 GB of memory, 650W power
supply, three hard disk drives, one graphics card, one LVD SCSI card).
All information in this section is based on primary power consumptions.
Table 1-4
System Power Specifications
Parameter
Total Rating
Peak
(15 sec)
Max. per PCI-X Sockets
64-bit, 133 MHz
Input voltage
100 – 240 VAC
Off
Off
Input current (max)
7.2A at 115 VAC or
3.6A at 220 VAC
Off
Off
Input frequency
50 to 60 Hz
Off
Off
Measured input power
560W
Off
Off
Available power (output)
650W
Off
85W total for PCI sockets
Max current at +12V
49A
0.5A
Off
Max current at –12V
0.35A
Off
0.1A
Max current at +3.3V
34A
Off
4.6A
Max current at +5V
18A
31A
3A
Max current at +3.3V
standby
3.5A
Off
Off
Table 1-5
Additional Component Power Consumption
Additional Component
Power Consumption
Processor
130W
443.6 Btu/h
SCSI hard disk drive (with I/O access)
23W
78.4 Btu/h