HP rp3440 Site Preparation Guide, Fifth Edition - HP 9000 rp3410/rp3440 - Page 33

Windows

Page 33 highlights

General Site Preparation Guidelines Facility Characteristics Table 2-3 Typical Raised Floor Specifications (Continued) Itema Rating Ultimate load 4,000 lb (1814 kg) per panel Rolling load 400 lb (181 kg) Average floor load 500 lb (227 kg) a. From Table 2-2 on page 31 b. With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Chapter 2 33

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47

General Site Preparation Guidelines
Facility Characteristics
Chapter 2
33
Windows
Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems.
Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight
places an additional load on the cooling system.
Ultimate load
4,000 lb (1814 kg) per panel
Rolling load
400 lb (181 kg)
Average floor load
500 lb (227 kg)
a. From Table 2-2 on page 31
b. With 0.08 in (0.2 cm) of span maximum deflection
Table 2-3
Typical Raised Floor Specifications (Continued)
Item
a
Rating