HP rp5400 Carrier Grade Addendum - rp5400 Series of Servers - Page 33
Cable Strain Relief, Safety Grounding, Cable Installation
View all HP rp5400 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 33 highlights
Installation Connecting the Server to DC Power Source Cable Strain Relief Figure 1-4 shows the power cables are secured to the bottom of the side tray with the cable tie wraps and attached to the front of the tray. Figure 1-4 Cable Installation Figure 1-5 shows the power cables are secured at the back of the tray by a strain relief bar. When connecting the power cables to the power source, ensure that there is enough slack in the cables to fully extend the tray. Figure 1-5 Cable Strain Relief Strain Relief Bar Strain Relief Sleeve Safety Grounding The rp5400 Series of Server Carrier Grade System has a grounding lug on the rear panel for connecting to earth ground. The server must be connected to earth ground using a minimum 6 AWG (16mm2) wire with a suitable Listed/Certified terminal such as Thomas and Betts part number 54205. Chapter 1 21