Honeywell NX4L1 Installation Guide - Page 21
Tying the Field Wiring in the NX4L1 Cabinet
View all Honeywell NX4L1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
NetAXS™ NX4L1 Installation Installation 4.2 Tying the Field Wiring in the NX4L1 Cabinet Use the following figure as a guide to secure the field wiring in the NX4L1 cabinet. Figure 2: Tying the Field Wiring in the NX4L1 Cabinet Location of wire tie points Pb Pb and suggested routing of Class 2 power-limited field wiring to maintain a minimum of 0.25 inch spacing from non-power- limited wiring . Wiring shown as represent shrink wrap barrier protection (0.028 inch thickness minimum) where spacing between non-power-limited and power-limited wiring is less than 0.25 inches. NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A 11
NetAXS™ NX4L1 Installation
Installation
NetAXS Access Control Unit NX4L1 Installation Guide
,
Document 7-901099, Revision A
11
4.2
Tying the Field Wiring in the NX4L1 Cabinet
Use the following figure as a guide to secure the field wiring in the NX4L1 cabinet.
Figure 2:
Tying the Field Wiring in the NX4L1 Cabinet
Pb
Pb
.
Wiring shown as ||||||||||||||||||||||||||||
represent shrink wrap barrier
protection (0.028 inch thickness
minimum) where spacing between
non-power-limited and power-limited
wiring is less than 0.25 inches.
Location of wire tie points
and suggested routing of
Class 2 power-limited field
wiring to maintain a
minimum of 0.25 inch
spacing from non-power-
limited wiring