Honeywell NX4L1 Installation Guide - Page 27
Supervised Input Wiring
View all Honeywell NX4L1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
NetAXS™ NX4L1 Installation Installation 4.5 Supervised Input Wiring The supervised inputs are located on TB4 and TB13 (Figure 8 on page 18). Input 1 through Input 8 may be configured for normally open or normally closed contacts as supervised or non-supervised. Inputs 13 and 14 are on TB8. All eight inputs have default functions, but they can be configured for general purpose inputs. The following table identifies the default function for each terminal position. Table 3 Default Supervised Input Assignments Terminal Position Default Function TB4-1 Door 1 REX (Egress) TB4-3 Door 1 Status TB4-4 Door 2 REX (Egress) TB4-6 Door 2 Status TB8-1 External Power Supply AC FAIL TB8-3 Panel Tamper TB13-1 Door 3 REX (Egress) TB13-3 Door 3 Status TB13-4 Door 4 REX (Egress) TB13-6 Door 4 Status TB 5-6, 6-6, 11-6, Optional supervised input if not used 12-6 for a reader tamper NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A 17