Honeywell NX4L1 Installation Guide - Page 32

RS-485 Communications

Page 32 highlights

NetAXS™ NX4L1 Installation Installation Figure 11: RS-232 Configuration Terminal COM1 CBL50 NetAXS Panel COM2 NetAXS Panel One NetAXS panel per COM port. Two COM ports possible. Reader 1 Reader 4 Reader 1 Reader 4 RS-485 Communications The NetAXS™ panel can reside on an existing RS-485 drop line hosted by either a NetAXS™ panel configured as a Gateway, or N-485-PCI-2, PCI-3, or N-485-HUB-2 (see Figure 12, Figure 13, and Figure 24). The interface allows the wiring of a Multidrop communication network of up to 4,000 feet (1200 m) in length. Only one host converter device per dropline is supported. Note: On a Multidrop Line, the Gateway panel and the PCI unit can have either end-point or interior positions. See Figure 20 on page 33 and Figure 21 on page 34. DIP switch position 6 on the NetAXS™ panel selects whether the panel is a Gateway or Multidrop panel. The switch in the OFF position configures the panel as a Multidrop panel; ON configures a Gateway. The panel must be power cycled for a new switch setting to be recognized. DIP switch positions 1-5 are used to select the panel's address on the network. Refer to Table 5 for DIP switch setting information. Connectors J36 and J37 are provided for supplying biasing and end-of-line termination for the RS-485 network. The board ships with all jumpers open. For a Multidrop RS-485 Line, you must close both J36 and J37 (terminated and biased) at the two end-point panels. At all other panels, leave J36 and J37 open. Both jumpers on a given panel must set the same. Note that biasing and termination on both ends are present. Use the jumpers on both ends of the RS-485 network. Note: If an RS-485 network has a NetAXS™ Gateway panel, no N1000-II, N1000-III, or N1000-IV are allowed on the same network. If they are added to a network with a NetAXS™ Gateway panel, they will not be able to communicate with the host computer. 22 www.honeywell.com

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79

22
www.honeywell.com
NetAXS™ NX4L1 Installation
Installation
Figure 11:
RS-232 Configuration
RS-485 Communications
The NetAXS™ panel can reside on an existing RS-485 drop line hosted by either a
NetAXS™ panel configured as a Gateway, or N-485-PCI-2, PCI-3, or N-485-HUB-2
(see
Figure 12
,
Figure 13
, and
Figure 24
). The interface allows the wiring of a
Multidrop communication network of up to 4,000 feet (1200 m) in length. Only one
host converter device per dropline is supported.
Note:
On a Multidrop Line, the Gateway panel and the PCI unit can have either
end-point or interior positions. See
Figure 20
on page 33 and
Figure 21
on page 34.
DIP switch position 6 on the NetAXS™ panel selects whether the panel is a Gateway
or Multidrop panel. The switch in the OFF position configures the panel as a
Multidrop panel; ON configures a Gateway. The panel must be power cycled for a
new switch setting to be recognized. DIP switch positions 1-5 are used to select the
panel’s address on the network. Refer to
Table 5
for DIP switch setting information.
Connectors J36 and J37 are provided for supplying biasing and end-of-line
termination for the RS-485 network. The board ships with all jumpers open. For a
Multidrop RS-485 Line, you must close both J36 and J37 (terminated and biased) at
the two end-point panels. At all other panels, leave J36 and J37 open. Both jumpers on
a given panel must set the same. Note that biasing and termination on both ends are
present. Use the jumpers on both ends of the RS-485 network.
Note:
If an RS-485 network has a NetAXS™ Gateway panel, no N1000-II, N1000-III,
or N1000-IV are allowed on the same network. If they are added to a network with a
NetAXS™ Gateway panel, they will not be able to communicate with the host
computer.
NetAXS
Panel
NetAXS
Panel
Reader 1
Reader 4
Reader 1
Reader 4
COM1
COM2
CBL50
One NetAXS panel per COM port. Two COM ports possible.
Terminal