Honeywell NX4L1 Installation Guide - Page 39

Table 6, MIRO 32/0 DIP Switch and Jumper Settings

Page 39 highlights

NetAXS™ NX4L1 Installation Installation Table 6 MIRO 32/0 DIP Switch and Jumper Settings (continued) Module Setting Value Jumper settings JP1 - CLOSED (if the module is the last module on the downstream bus), OPEN (if the module is not the last module on the downstream bus) JP2 - any setting JP3 - any setting JP4 - NORMAL (Positions 1 and 2) MIRO 2/16 DIP switches Address (switches 1-6) - 3 through 6 Baud rate (switches 7 and 8) - 7 = OFF, 8 = ON OP Mode (switches 9 and 10) - 9 = OFF, 10 = OFF Jumper settings JP1 - CLOSED, positions 2 and 3 (if the module is the last module on the downstream bus); OPEN, positions 1 and 2 (if the module is not the last module on the downstream bus) JP2 - NORMAL, positions 1 and 2 Note: If a MIRO 32/0 is not required in a system, start addressing the 2/16 modules at DIP switch 3. If a MIRO 32/0 is configured with an address other than 1 or 2, the NetAXS™ panel will not communicate with it. Likewise, if a MIRO 2/16 is configured with an address other than 3 through 6, the NetAXS™ panel will not communicate with it. The NetAXS™ board and the NX4L1 is not intended to provide either module power or module output load power for downstream I/O. A separate 24 VDC supply should be used to provide power to all downstream modules and output loads. For some installations, the noise immunity improves if the NetAXS™ common is connected to the 24 V Return wiring for the downstream modules. This connection is not needed for most installations. NetAXS Access Control Unit NX4L1 Installation Guide, Document 7-901099, Revision A 29

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79

NetAXS™ NX4L1 Installation
Installation
NetAXS Access Control Unit NX4L1 Installation Guide
,
Document 7-901099, Revision A
29
Note:
If a MIRO 32/0 is not required in a system, start addressing the 2/16 modules at
DIP switch 3. If a MIRO 32/0 is configured with an address other than 1 or 2, the
NetAXS™ panel will not communicate with it. Likewise, if a MIRO 2/16 is
configured with an address other than 3 through 6, the NetAXS™ panel will not
communicate with it.
The NetAXS™ board and the NX4L1 is not intended to provide either module power
or module output load power for downstream I/O. A separate 24 VDC supply should
be used to provide power to all downstream modules and output loads. For some
installations, the noise immunity improves if the NetAXS™ common is connected to
the 24 V Return wiring for the downstream modules. This connection is not needed
for most installations.
Jumper settings
JP1 - CLOSED (if the module is
the last module on the
downstream bus), OPEN (if the
module is not the last module on
the downstream bus)
JP2 - any setting
JP3 - any setting
JP4 - NORMAL
(Positions 1 and 2)
MIRO 2/16
DIP switches
Address (switches 1-6) - 3
through 6
Baud rate (switches 7 and 8) - 7
= OFF, 8 = ON
OP Mode (switches 9 and 10) - 9
= OFF, 10 = OFF
Jumper settings
JP1 - CLOSED, positions 2 and
3 (if the module is the last
module on the downstream bus);
OPEN, positions 1 and 2 (if the
module is not the last module on
the downstream bus)
JP2 - NORMAL, positions 1
and 2
Table 6
MIRO 32/0 DIP Switch and Jumper Settings
(continued)
Module
Setting
Value