Honeywell T7351F2010 Installation Instructions - Page 6

Discharge High Limit Only displayed if Discharge Air Sensor is Selected - commercial thermostat

Page 6 highlights

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 3. Installer Setup. (Continued) Text Default Choices Notes TMP LIM 3 0 - 5 TMP OCC 3 TMP CAL 0 1 - 8 -4 - 3 MINCOOL 45° F 45° - 99° F (7° C) (7° - 37° C) MAXHEAT 90° F 40° - 90° F (32° C) (4° - 32°) HEATLCK NO YES or NO HTLCKSP 70° F -40° - 120 ° F (21° C) (-40° - 49° F) COOLLCK NO YES or NO CLLCKSP DAT LL 35° F (2° C) NO -40° - 120° F (-40° - 49° C) YES or NO DATLLSP DAT HL 45° F (7° C) NO 35° - 60° F (2° - 16° C) YES or NO DATHLSP 110° F 65° - 140° F (43° C) (18° - 60° C) DEHUMID 0 0 - 5 DEH MIN 5 DEH TMP 2 MINHTRT 5 MAXHTRT 8 5 - 15 1 - 5 0 - 20 DDF/HR 0 - 20 DDF/HR MINHTOA 0° F (-18° C) MAXHTOA 40° F (4° C) MINCLRT 3 -20° - 120° F (-29° - 49° C) -20° - 120° F (-29° - 49° C) 0 - 20 DDF/HR Temporary Setpoint Adjustment 0: 0 Deg. F 1: 1 Deg. F 2: 2 Deg. F 3: 3 Deg. F 4: 4 Deg. F 5: 5 Deg. F Temporary Occupied Duration 1 to 8 hours Temporary Display Adjustment 0 - 3 = 0 to 3 DDF 4 - 7 = -4 to -1 DDF Min Cool Setpoint Max Heat Setpoint Heating Lockout (Only displayed if Outdoor Air Sensor is selected) NO: None YES: Enabled Heating Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) Cooling Lockout (Only displayed if Outdoor Air Sensor is Selected) NO: None YES: Enabled Cooling Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) Discharge Low Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled Discharge Low Temp Limit (Display only if Discharge Sensor is configured) Discharge High Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled Discharge High Temperature Limit (Display only if Discharge Sensor is configured) Dehumidification 0: None 1: MinOn Time 2: Reset Temp Setpoint 3: Reset w/ MinOn 4: Reheat 5: Reheat w/ Min On Dehumidify Minutes On Dehumidify Temp Reset Minimum Heat Recovery Ramp Rate Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) Minimum Cool Recovery Ramp Rate MAXCLRT MINCLOA 6 0 - 20 DDF/HR 90° F -20° - 120° F (32° C) (-29° - 49° C) Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) MAXCLOA 70° F -20° - 120° F Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is (21° C) (-29° - 49° C) Selected) 62-0258-05 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
62-0258—05
6
TMP LIM
3
0 - 5
Temporary Setpoint Adjustment
0: 0 Deg. F
1: 1 Deg. F
2: 2 Deg. F
3: 3 Deg. F
4: 4 Deg. F
5: 5 Deg. F
TMP OCC
3
1 - 8
Temporary Occupied Duration
1 to 8 hours
TMP CAL
0
-4 - 3
Temporary Display Adjustment
0 - 3 = 0 to 3 DDF
4 - 7 = -4 to -1 DDF
MINCOOL
45° F
(7° C)
45° - 99° F
(7° - 37° C)
Min Cool Setpoint
MAXHEAT
90° F
(32° C)
40° - 90° F
(4° - 32°)
Max Heat Setpoint
HEATLCK
NO
YES or NO
Heating Lockout (Only displayed if Outdoor Air Sensor is selected)
NO: None
YES: Enabled
HTLCKSP
70° F
(21° C)
-40° - 120 ° F
(-40° -
49° F)
Heating Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
COOLLCK
NO
YES or NO
Cooling Lockout (Only displayed if Outdoor Air Sensor is Selected)
NO: None
YES: Enabled
CLLCKSP
35° F
(2° C)
-40° - 120° F
(-40° - 49° C)
Cooling Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
DAT LL
NO
YES or NO
Discharge Low Limit (Only displayed if Discharge Air Sensor is Selected)
NO: None
YES: Enabled
DATLLSP
45° F
(7° C)
35° - 60° F
(2° - 16° C)
Discharge Low Temp Limit
(Display only if Discharge Sensor is configured)
DAT HL
NO
YES or NO
Discharge High Limit (Only displayed if Discharge Air Sensor is Selected)
NO: None
YES: Enabled
DATHLSP
110° F
(43° C)
65° - 140° F
(18° - 60° C)
Discharge High Temperature Limit
(Display only if Discharge Sensor is configured)
DEHUMID
0
0 - 5
Dehumidification
0: None
1: MinOn Time
2: Reset Temp Setpoint
3: Reset w/ MinOn
4: Reheat
5: Reheat w/ Min On
DEH MIN
5
5 - 15
Dehumidify Minutes On
DEH TMP
2
1 - 5
Dehumidify Temp Reset
MINHTRT
5
0 - 20 DDF/HR
Minimum Heat Recovery Ramp Rate
MAXHTRT
8
0 - 20 DDF/HR
Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is
Selected)
MINHTOA
0° F
(-18°
C)
-20° - 120° F
(-29° - 49° C)
Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
MAXHTOA
40° F
(4° C)
-20° - 120° F
(-29° - 49° C)
Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
MINCLRT
3
0 - 20 DDF/HR
Minimum Cool Recovery Ramp Rate
MAXCLRT
6
0 - 20 DDF/HR
Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is
Selected)
MINCLOA
90° F
(32° C)
-20° - 120° F
(-29° - 49° C)
Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
MAXCLOA
70° F
(21° C)
-20° - 120° F
(-29° - 49° C)
Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Table 3. Installer Setup.
(Continued)
Text
Default
Choices
Notes