Honeywell T7351F2010 Installation Instructions - Page 8

Special Functions, Restore Factory Configuration Run, Clear, Get Factory Schedule Info/Clear

Page 8 highlights

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Grouping Temperature Set Override Schedule Table 5. T7351 Key Function Summary. (Continued) Button Definition Occupied Heat Occupied Cool Not Occupied Heat Not Occupied Cool Sets Occupied Heat setpoint. Sets Occupied Cool setpoint. Sets Not Occupied Heat setpoint. Sets Not Occupied Cool setpoint. Day Time Temporary Occupied Temporary Not Occupied Day Sets day of week. Tapping key with 'Set Value' segment on increases current day (same effect as Up Arrow key). Sets time. Tapping key with "Set Value" segment on increases time in one hour increments. Temporary occupied setting for length of time defined by installer. User can modify setpoints. Sets holiday length. User selects number of days ("0"-"99"), or "---" for continuous override. Selects day schedule to modify. (Used also with copy key.) Occupied Not Occupied Clear Start Time Selects occupied event start times for specified day. Repeatedly press this key to toggle between two occupied events. Selects not occupied event start times for specified day. Repeatedly press this key to toggle between two not occupied events. Clears start time for specified period and day. Copy Copies schedule from one day to another. System Selects System Mode. Toggles through Em Heat, Heat, Off, Cool, and Auto. Fan Selects fan operation mode. Toggles between On and Auto.a Run Schedule Resumes running schedule (cancels Temporary Occupied action, Holiday, and/or Temporary setpoint changes.) a On: Continuous fan operation during occupied periods. During not occupied periods and in standby mode when no motion is sensed, fan cycles with call for heat or cool. Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details). NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress): - ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ. - one minute: when returning from setting clock/day. - ten minutes: when returning from System Checkout. - five minutes: when returning from all other modes. Special Functions Restore Factory Configuration (Run/ Clear) IMPORTANT This operation erases current configuration and restores factory defaults for all configuration, parameters, setpoints and schedules. To regain the old requires device reconfiguration. 1. Press both Run Schedule and Clear Start Time. 2. The display gives the option to revert to FAC CFG. a. To restore the factory defaults, press up or down until the display indicates YES. b. To cancel this option, ensure the display indicates NO. 3. Press Run Schedule. Get Factory Schedule (Info/Clear) Performing this operation reverts the schedules to the factory defaults: 1. Press both Info and Clear Start Time. 2. The display gives the option to revert to FAC SCH. a. To restore the factory schedule, press up or down until the display indicates YES. b. To cancel this option, ensure display indicates NO. 3. Press Run Schedule. 62-0258-05 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
62-0258—05
8
a
On: Continuous fan operation during occupied periods. During not occupied periods and in standby mode when no
motion is sensed, fan cycles with call for heat or cool.
Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details).
NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress):
ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ.
one minute: when returning from setting clock/day.
ten minutes: when returning from System Checkout.
five minutes: when returning from all other modes.
Special Functions
Restore Factory Configuration (Run/
Clear)
IMPORTANT
This operation erases current configuration and
restores factory defaults for all configuration,
parameters, setpoints and schedules. To regain
the old requires device reconfiguration.
1.
Press both
Run Schedule
and
Clear Start
Time
.
2.
The display gives the option to revert to FAC CFG.
a.
To restore the factory defaults, press up
±
or
down
²
until the display indicates YES.
b.
To cancel this option, ensure the display
indicates NO.
3.
Press
Run Schedule.
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the
factory defaults:
1.
Press both
Info
and
Clear Start
Time
.
2.
The display gives the option to revert to FAC SCH.
a.
To restore the factory schedule, press up
±
or
down
²
until the display indicates YES.
b.
To cancel this option, ensure display indicates
NO.
3.
Press
Run Schedule.
Temperature
Occupied
Heat
Sets Occupied Heat setpoint.
Occupied
Cool
Sets Occupied Cool setpoint.
Not
Occupied
Heat
Sets Not Occupied Heat setpoint.
Not
Occupied
Cool
Sets Not Occupied Cool setpoint.
Set
Day
Sets day of week. Tapping key with 'Set Value' segment on increases current
day (same effect as
Up Arrow
key).
Time
Sets time. Tapping key with “Set Value” segment on increases time in one
hour increments.
Override
Temporary
Occupied
Temporary occupied setting for length of time defined by installer. User can
modify setpoints.
Temporary Not
Occupied
Sets holiday length. User selects number of days (“0”-”99”), or “---” for
continuous override.
Schedule
Day
Selects day schedule to modify. (Used also with copy key.)
Occupied
Selects occupied event start times for specified day. Repeatedly press this
key to toggle between two occupied events.
Not Occupied
Selects not occupied event start times for specified day. Repeatedly press
this key to toggle between two not occupied events.
Clear Start Time
Clears start time for specified period and day.
Copy
Copies schedule from one day to another.
System
Selects System Mode. Toggles through Em Heat, Heat, Off, Cool, and Auto.
Fan
Selects fan operation mode. Toggles between On and Auto.
a
Run Schedule
Resumes running schedule (cancels Temporary Occupied action, Holiday,
and/or Temporary setpoint changes.)
Table 5. T7351 Key Function Summary. (Continued)