Honeywell T8401C1015 Installation Instructions - Page 3

Fig. 5. Wiring connections - thermostat

Page 3 highlights

T8400C, T8401C ELECTRONIC THERMOSTATS KEEP WIRING IN SHADED AREA G Rc R W B Y O MOUNTING SCREW HOLE WIRING ENTRANCE HOLE MOUNTING SCREW HOLE M16432 Fig. 4. Restrict wiring to shaded area (T8400C shown). TERMINAL SCREW G FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM) FOR WRAPAROUND STRIP 7/16 IN. (11 MM) Rc R W Y B O M13274 Fig. 5. Wiring connections (T8400C shown). G Rc 2 R W B Y O COOLING CONTACTOR 1 L1 (HOT) 24V L2 HEATING PRIMARY CONTROL FAN RELAY 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER. M13275 Fig. 6. Typical hookup of T8400C in heat-cool system with single transformer. G Rc R 24 W B Y O 1 L1 (HOT) L2 FAN RELAY 3 COOL DAMPER 3 HEAT DAMPER COMPRESSOR CONTACTOR HEAT RELAY 1 L1 (HOT) L2 COOLING TRANSFORMER HEATING TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO TRANSFORMER SYSTEM. 3 CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS. 4 POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH IS IN THE OFF POSITION. M12562A Fig. 7. Typical hookup of T8400C in heat-cool system with two transformers. G Rc 3 R W 4 Y 2 HEAT CHANGEOVER B 2 COOL O CHANGEOVER 1 L1 (HOT) 24V L2 TRANSFORMER COMPRESSOR FAN RELAY 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS. 3 FACTORY INSTALLED JUMPER. 4 FIELD INSTALLED JUMPER. M20880 Fig. 8. Typical hookup of T8400C in single-stage heat pump systems. 3 69-1740

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

T8400C, T8401C ELECTRONIC THERMOSTATS
3
69-1740
Fig. 4. Restrict wiring to shaded area
(T8400C shown).
Fig. 5. Wiring connections
(T8400C shown).
Fig. 6. Typical hookup of T8400C in heat-cool system
with single transformer.
Fig. 7. Typical hookup of T8400C in heat-cool system
with two transformers.
Fig. 8. Typical hookup of T8400C in single-stage heat
pump systems.
KEEP WIRING IN
SHADED AREA
MOUNTING
SCREW HOLE
MOUNTING
SCREW HOLE
WIRING ENTRANCE
HOLE
M16432
G
Rc
R
Y
W
B
O
TERMINAL
SCREW
M13274
G
Rc
R
Y
W
B
O
FOR STRAIGHT INSERTION
STRIP 5/16 IN. (8 MM)
FOR WRAPAROUND
STRIP 7/16 IN. (11 MM)
L1
(HOT)
L2
1
1
COOLING
CONTACTOR
FAN
RELAY
HEATING
PRIMARY
CONTROL
24V
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
M13275
Y
G
Rc
W
R
B
O
2
2
Y
G
Rc
W
2
4
R
B
O
FAN
RELAY
HEAT
RELAY
COMPRESSOR
CONTACTOR
HEATING
TRANSFORMER
COOLING
TRANSFORMER
HEAT
DAMPER
COOL
DAMPER
3
3
L1
(HOT)
L2
1
L1
(HOT)
L2
1
M12562A
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
REMOVE RC TO R JUMPER WHEN INSTALLED ON A TWO
TRANSFORMER SYSTEM.
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
POWER TO R TERMINAL IS REQUIRED WHEN THE SYSTEM SWITCH
IS IN THE OFF POSITION.
2
3
4
L1
(HOT)
L2
1
COOL
CHANGEOVER
FAN
RELAY
COMPRESSOR
24V
M20880
HEAT
CHANGEOVER
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
CAN BE USED FOR CHANGEOVER VALVE ON
SINGLE-STAGE HEAT PUMP SYSTEMS.
FACTORY INSTALLED JUMPER.
FIELD INSTALLED JUMPER.
2
3
4
4
2
2
Y
G
Rc
W
R
B
O
3