RS485 Bus FAQ
View all IC Realtime ICIP-P2012T manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
Figure 7-2 7.4 RS485 Bus FAQ Phenomenon Speed dome can run selfdiagnosis but I can not control it. I can control the speed dome but is not smooth Possible Reasons z Host address(baud rate) and speed dome address(baud rate) are not match; z Positive and negative end of RS485 Bus are misconnected; z Connection cable is loose; z RS485 Bus connection are cut off; z RS485 Bus connection are not good; z One RS485 bus is off; z The distance between host and speed dome is too far; z Parallel connected too much speed domes. Solution z Modify host or speed dome setup ; z Switch RS485 positive end and negative end; z Fix connection cable firmly; z Replace RS485 Bus. z Connect RS 485 Bus again; z Replace RS485 Bus; z Add terminal matching resistance; z Add RS485 distributor. 18