LG ARUN096BT2 Installation Manual - Page 24

Pipe length between Outdoor Units, Gas pipe, Liquid pipe, High/Low Pressure Common pipe

Page 24 highlights

Refrigerant piping installation 12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling performance, drip of condensate and other such problems. 13. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor Units has been connected, a refrigerant leakage test has been performed and the evacuation process has been completed. 14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant oil. WARNING When installing and moving the air conditioner to another site, be sure to make recharge refrigerant after perfect evacuation. - If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged. - After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the installation pipe drawing. Pipe length between Outdoor Units (Gas pipe, Liquid pipe, High/Low Pressure Common pipe) = Product length + ∑ 10(0.4) (distance between Outdoor Units) Unit : mm(inch) Product length 10(0.4) Distance between Outdoor Units Product length 10(0.4) Distance between Outdoor Units 24 Outdoor Unit

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91

24
Outdoor Unit
Refrigerant piping installation
WARNING
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant
after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and
the unit may be damaged.
- After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after
branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the
installation pipe drawing.
Product length
Distance between Outdoor Units
10(0.4)
10(0.4)
Product length
Distance between Outdoor Units
Unit : mm(inch)
= Product length +
10(0.4) (distance between Outdoor Units)
Pipe length between Outdoor Units
(Gas pipe, Liquid pipe, High/Low Pressure Common pipe)
12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor-
mance, drip of condensate and other such problems.
13. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor
Units has been connected, a refrigerant leakage test has been performed and the evacuation process
has been completed.
14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant
oil.