LG ARUN096BT2 Installation Manual - Page 39

Branch pipe Fitting

Page 39 highlights

ENGLISH Branch pipe Fitting Refrigerant piping installation Y branch A B A To Outdoor Unit B To Branch Piping or Indoor Unit • Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Horizontal plane Facing downwards Facing upwards Within +/- 10° A Viewed from point A in direction of arrow Within ± 3° Within ± 3° • There is no limitation on the joint mounting configuration. • If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter. • Branch pipe should be insulated with the insulator in each kit. Tape (field supply) Header Insulator (included with kit) Liquid and gas pipe joints A B C Insulator for field piping A To outdoor unit B To indoor unit • The indoor unit having larger capacity must be installed closer to than smaller one. • If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter. Pipe cutter • When the number of pipes to be connected is smaller than the number of header branches, install a cap to the unconnected branches. Installation Manual 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91

Installation Manual
39
ENGLISH
Refrigerant piping installation
Branch pipe Fitting
Y branch
A
B
To Outdoor Unit
To Branch Piping or Indoor Unit
A
B
Facing
upwards
Facing
downwards
Within
±
3
°
Within
±
3
°
Viewed from point A
in direction of arrow
Horizontal
plane
Within +/- 10
°
A
Insulator
(included with kit)
Liquid and gas
pipe joints
Insulator for
field piping
Tape
(field supply)
A
B
Header
To outdoor unit
To indoor unit
A
B
C
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
• When the number of pipes to be connected is
smaller than the number of header branches,
install a cap to the unconnected branches.
• The indoor unit having larger capacity must be
installed closer to
than smaller one.
• If the diameter of the refrigerant piping selected
by the procedures described is different from
the size of the joint,
the connecting section
should be cut with a pipe cutter.
Pipe cutter