LG LCU240CP Service Manual - Page 25
Installation of Decoration Panel
View all LG LCU240CP manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Installation 5. Installation of Decoration Panel The decoration panel has its installation direction. Before installing the decoration panel, always remove the paper template. 1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm(0.39inch) in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Air conditioner unit Piping side Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm(0.39inch)) ILnoluevterGmroiltloer Decoration panel Key holes Decoration panel fixing screws (Hexagon M5 screw) Control box cover Display Lead wire for louver motor and display CAUTION Inlet Grille Install certainly the decoration panel. Good example Cool air leakage causes sweating. Water drops fall. Bad example Air conditioner unit Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage Air conditioner unit Air Cool air leakage (no good) Ceiling board Decoration panel Service Manual 25