Maytag CWG3100AAE Installation Instructions - Page 9

Gas Conversions - lp conversion

Page 9 highlights

GAS CONVERSIONS Gas conversions from Natural gas to LP gas or from LP gas to Natural gas must be done by a qualified installer. To Convert Gas Pressure Regulator WARNING 1. Locate gas pressure regulator in bottom compartment. AB C Explosion Hazard Use a new CSA International approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to LP, have a qualified person make sure gas pressure does not exceed 14" (36 cm) water column. Examples of a qualified person include: licensed heating personnel, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire. LP Gas Conversion 1. Turn manual shutoff valve to the closed position. 2. Unplug oven or disconnect power. B A C A. To oven B. Shutoff valve (closed position) C. Gas supply line G F E D A. Gas pressure regulator B. Gas supply line C. Electrical disconnect D. Serial plate E. Manual oven valve F. Burner rating plate G. Manifold pressure tap IMPORTANT: Do not remove the gas pressure regulator. 2. Unscrew the hex-shaped regulator cap from the regulator and remove the regulator pin. A B A. Regulator pin B. Regulator cap 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

9
GAS CONVERSIONS
Gas conversions from Natural gas to LP gas or from LP gas to
Natural gas must be done by a qualified installer.
LP Gas Conversion
1.
Turn manual shutoff valve to the closed position.
2.
Unplug oven or disconnect power.
To Convert Gas Pressure Regulator
1.
Locate gas pressure regulator in bottom compartment.
IMPORTANT:
Do not remove the gas pressure regulator.
2.
Unscrew the hex-shaped regulator cap from the regulator and
remove the regulator pin.
A. To oven
B. Shutoff valve (closed position)
C. Gas supply line
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
A
B
C
A. Gas pressure regulator
B. Gas supply line
C. Electrical disconnect
D. Serial plate
E. Manual oven valve
F. Burner rating plate
G. Manifold pressure tap
A. Regulator pin
B. Regulator cap