Tripp Lite 9PXEBM180RT Eaton 9PX 5000 9PX 6000 9PX 6000 G 9PX EMB 180 V Instal - Page 24
Power cables connection
View all Tripp Lite 9PXEBM180RT manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 24 highlights
4. Power cables connection 4.1 Access to terminal blocks 1. Remove the terminal blocks cover (one screw) 2. Punch the knockouts and insert the cables/conduits inside Note: the L6-30P input power cable is attached by Eaton. 9PX 6000 G only • High leakage current: Earth connection essential before connecting supply. 4.2 Input/Output connection This type of connection must be carried out by qualified electrical personnel Before carrying out any connection, check that the upstream protection device (Normal AC source) is open "O" (Off). Always connect the ground wire first If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the terminal blocks connection of the UPS with this accessory. L1 N(L2) NORMAL AC SOURCE t 1. Insert the Normal AC cable through the cable gland. 2. C onnect the three cables to the Normal AC source terminal blocks. 3. Insert the Output cable through the cable gland. 4. C onnect the three cables to the Output terminal blocks. 5. P ut back and secure the terminal blocks cover with the screw. 6. Tighten the cable glands. L1 N(L2) OUTPUT t Page 24 5-6kVA US_EN