Tripp Lite 9PXEBM180RT Eaton 9PX 5000 9PX 6000 9PX 6000 G 9PX EMB 180 V Instal - Page 4

Special precautions

Page 4 highlights

SAFETY INSTRUCTIONS Special precautions • The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations. • All handling operations will require at least two people (unpacking, lifting, installation in rack sys- tem). • Straps are provided only for unpacking manually the unit from the carton; don't use the straps to carry the unit around. The unit can slip from the straps during handling (risk of injury and product damage): - keep 12in / 30cm minimum distance between the straps - lift the unit carefully and keep it at low height - keep the unit horizontal during unpacking. • Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage. • During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don't hesitate to contact your EATON representative. • All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS. Page 4 5-6kVA US_EN

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 4
5-6kVA US_EN
SAFETY INSTRUCTIONS
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations.
All handling operations will require at least two people (unpacking, lifting, installation in rack sys-
tem).
Straps are provided only for unpacking manually the unit from the carton; don’t use the straps to
carry the unit around. The unit can slip from the straps during handling (risk of injury and product
damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must
be energized for a period of 24 hours, at least once every 6 months (for a normal storage tempera-
ture less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the UPS.