Tripp Lite 9PXEBM180RT Eaton 9PX 5000 9PX 6000 9PX 6000 G 9PX EMB 180 V Instal - Page 43

Table 10. Communication options

Page 43 highlights

ENGLISH 9. Specifications Agency markings Operating temperature Storage temperature Transit temperature Relative humidity Operating altitude Transit altitude Audible noise CE / cULus / NOM 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude Note: thermal protection switches load to Bypass in case of overheating. 0 to 40°C (32 to 104°F) with batteries -15 to 60°C (5 to 140°F) without batteries -25 to 55°C (-13 to 130°F) 0 to 95% no condensing Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m Up to 10,000 meters (32,808 ft) above sea level < 45 dBA at 1 meter typical Table 9. Battery Rack / Tower configuration Type Monitoring Battery port EBM battery cable length Internal batteries 5000/6000VA: 180Vdc EBM 9PXEBM180RT: 180Vdc Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F). Lifetime is reduced above 30 °C. Advanced monitoring for earlier failure detection and warning External three-pole SBS75G Black connector on UPS for connection to EBM 40cm (15.7in) Table 10. Communication options Communication bay Compatible connectivity cards Communication ports Relay output contacts Remote On/Off Remote Power Off (1) available independent communication bay for connectivity cards Network-MS Modbus-MS Relay-MS RS-232 (DB9): 1200-19200 bps USB: 19200 bps (4) relay outputs (normally open or normally closed) 2 pins jumper (normally open) 3 pins jumper (normally open or normally closed) 5-6kVA US_EN Page 43

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 43
5-6kVA US_EN
ENGLISH
9. Specifications
Agency markings
CE / cULus / NOM
Operating temperature
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note:
thermal protection switches load to Bypass in case of overheating.
Storage temperature
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible noise
< 45 dBA at 1 meter typical
Table 9. Battery
Internal batteries
EBM
Rack / Tower
configuration
5000/6000VA: 180Vdc
9PXEBM180RT: 180Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30 °C.
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery port
External three-pole SBS75G Black connector on UPS for connection to EBM
EBM battery
cable length
40cm (15.7in)
Table 10. Communication options
Communication bay
(1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Relay output contacts
(4) relay outputs (normally open or normally closed)
Remote On/Off
2 pins jumper (normally open)
Remote Power Off
3 pins jumper (normally open or normally closed)