Asko DC7583 User manual 427000608 ASKO DC7573 EN - Page 13

Connection to the exhaust duct, The drying cabinet can be connected to the exhaust duct in two ways: - appliances

Page 13 highlights

Vent connection Connection to the exhaust duct When the cabinet is on, 1589 ft3 (45 m3) moist air/hour is evacuated. Make sure that air can enter the room to replace the moist air that has been vented. WARNING! • The drying cabinet must not be connected to the duct for flue gases. Exhaust duct Only a rigid or flexible metal duct shall be used for exhausting. The exhaust duct diameter both in Canada and United States shall be 4" (102mm) ridged metal exhaust duct. Run the duct with as few bends as possible. In Canada, only those foil-type ducts, if any, specifically identified for use with the appliance by the manufacturer shall be used. In the United States, only those foil-type ducts, if any, specifically identified for use with the appliance by the manufacturer and which comply with the Outline for Clothes Dryer Transition Duct, Subject 2158A, shall be used. The maximum length of a flexible duct is 40" (1.0m). The drying cabinet can be connected to the exhaust duct in two ways: With draft check The existing valve is replaced with the draft check (supplied with the cabinet). Do not fit valves found in the building's ventilation system inside the drying cabinet. 1. Moist air out 2. Hose (not included) 3. Connector (not included) 4. Draft check 4 1 2 3 The drying cabinet is connected to the exhaust duct using the draft check Customer Care Center 11 1-800-898-1879 www.askousa.com

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Connection to the exhaust duct
When the cabinet is on, 1589 ft
3
(45 m
3
) moist
air/hour is evacuated. Make sure that air can enter
the room to replace the moist air that has been
vented.
WARNING!
The drying cabinet must not be connected to
the duct for flue gases.
Exhaust duct
Only a rigid or flexible metal duct shall be used
for exhausting. The exhaust duct diameter both
in Canada and United States shall be 4" (102mm)
ridged metal exhaust duct. Run the duct with as
few bends as possible.
In Canada, only those foil-type ducts, if any,
specifically identified for use with the appliance
by the manufacturer shall be used. In the United
States, only those foil-type ducts, if any,
specifically identified for use with the appliance
by the manufacturer and which comply with the
Outline for Clothes Dryer Transition Duct, Subject
2158A, shall be used.
The maximum length of a flexible duct is 40"
(1.0m).
The drying cabinet can be connected to
the exhaust duct in two ways:
With draft check
The existing valve is replaced with the draft check
(supplied with the cabinet).
Do not fit valves found in the building’s ventilation
system inside the drying cabinet.
1. Moist air out
2. Hose (not included)
3. Connector (not included)
4. Draft check
1
2
3
4
The drying cabinet is connected to the exhaust duct using the draft
check
11
Customer Care Center
1-800-898-1879
www.askousa.com
Vent connection