Electrical Connection of ERD Series Ranges, continued

Page 10 highlights

Installation Instructions Electrical Connection of ERD Series Ranges (continued) Connecting to a Three-Wire Electrical System (where local codes permit) Cable from power supply WARNING Do not connect the green appliance wire to the neutral (white) supply wire unless local building codes permit. 1. Make sure power to the junction box is switched off at the circuit breaker or fuse box. 2. Connect the green and white appliance wires to the neutral (white) supply wire in the junction box. 3. Connect the black appliance wire to the black (L1) power supply wire in the junction box. 4. Connect the red appliance wire to the red (L2) power supply wire in the junction box. RED RED GREEN WHITE WHITE BLACK BLACK Junction box Wire nut (3 places) Conduit from appliance Connecting the Appliance to a Three-Wire Power Supply (where local codes permit) Connecting to a Four-Wire Electrical System with External Ground (where local codes permit) WARNING Do not ground the appliance to a gas supply pipe or hot water pipe. A grounded cold water pipe must have metal continuity to electrical ground and must not be interrupted by insulating materials. Any insulating materials must be jumped with a length of No. 4 copper wire securely clamped to bare metal at both ends. 1. Make sure power to the junction box is switched off at the circuit breaker or fuse box. 2. Separate the green and white appliance wires. 3. Connect the white appliance wire to the neutral (white) supply wire in the junction box. 4. Connect the black appliance wire to the black (L1) power supply wire in the junction box. 5. Connect the red appliance wire to the red (L2) power supply wire in the junction box. 6. Connect the green appliance wire to a grounded supply wire in the junction box or to a grounded cold water pipe. If connecting to a grounded cold water pipe, a separate copper grounding wire (No. 10 minimum) must be connected to a grounded cold water pipe by means of a clamp and then to an external grounding connector screw. Cable from power supply RED RED GREEN GREEN WHITE WHITE BLACK BLACK Junction box Wire nut (4 places) Separate No. 10 (minimum) copper grounding wire No. 4 copper wire Meter Clamp must be tight on pipe Metal water pipe Clamps Bare metal Conduit from appliance Connecting the Appliance Ground to a Grounded Junction Box Wire or Grounded Cold Water Pipe 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

8
Installation Instructions
Conduit from
appliance
Cable from
power supply
Wire nut
(3 places)
Junction
box
RED
RED
GREEN
WHITE
WHITE
BLACK
BLACK
Connecting the Appliance to a
Three-Wire Power Supply (where local codes permit)
Connecting to a Four-Wire Electrical System with
External Ground (where local codes permit)
WARNING
Do not ground the appliance to a gas supply pipe or hot water
pipe.
A grounded cold water pipe must have metal continuity to
electrical ground and must not be interrupted by insulating
materials. Any insulating materials must be jumped with a length
of No. 4 copper wire securely clamped to bare metal at both ends.
Make sure power to the junction box is switched off at the
1.
circuit breaker or fuse box.
Separate the green and white appliance wires.
2.
Connect the white appliance wire to the neutral (white) supply
3.
wire in the junction box.
Connect the black appliance wire to the black (L1) power
4.
supply wire in the junction box.
Connect the red appliance wire to the red (L2) power supply
5.
wire in the junction box.
Connect the green appliance wire to a grounded supply
6.
wire in the junction box or to a grounded cold water pipe. If
connecting to a grounded cold water pipe, a separate copper
grounding wire (No. 10 minimum) must be connected to a
grounded cold water pipe by means of a clamp and then to
an external grounding connector screw.
Connecting the Appliance Ground to a Grounded Junction Box Wire or Grounded Cold Water Pipe
Conduit from
appliance
Cable from
power supply
Wire nut
(4 places)
Junction
box
RED
RED
GREEN
GREEN
WHITE
WHITE
BLACK
BLACK
Separate No. 10 (minimum)
copper grounding wire
Clamp must be
tight on pipe
No. 4
copper wire
Metal
water pipe
Clamps
Bare metal
Meter
Electrical Connection of ERD Series Ranges
(continued)
Connecting to a Three-Wire Electrical System
(where local codes permit)
WARNING
Do not connect the green appliance wire to the neutral (white)
supply wire unless local building codes permit.
Make sure power to the junction box is switched off at the
1.
circuit breaker or fuse box.
Connect the green and white appliance wires to the neutral
2.
(white) supply wire in the junction box.
Connect the black appliance wire to the black (L1) power
3.
supply wire in the junction box.
Connect the red appliance wire to the red (L2) power supply
4.
wire in the junction box.