Dell N3200-ON External Power Supply Installation PowerSwitch N2200-ON and N320 - Page 11

Visual display workplaces

Page 11 highlights

NOTE: Coat the one-hole lug with an antioxidant compound before crimping. Also, bring any unplated mating surfaces to a shiny finish and coat with an before mating. Plated mating surfaces must be clean and free from contamination. NOTE: The rack installation ears are not suitable for grounding. To connect the ground cable to the switch: 1. Cut your user-supplied ground cable to the wanted length. The cable length must facilitate proper operation of the fault interrupt circuits. Use the shortest cable route allowable. 2. Crimp the ground cable inside the preinstalled ground lug. 3. Attach the other end of the ground cable to a suitable ground point such as the rack or cabinet. NOTE: Always secure the DC output cable to the output terminal block when EPS operating. Visual display workplaces This device is not intended for use in the direct field of view at visual display workplaces. To avoid incommoding reflexions at visual display workplaces this device must not be placed in the direct field of view. Bemerkung: Dieses Gerät ist nicht für den Einsatz im direkten Sichtfeld am Bildschirmarbeitsplatz vorgesehen. Um störende Reflexionen am Bildschirmarbeitsplatz zu vermeiden, darf dieses Gerät nicht im direkten Sichtfeld platziert werden. N-Series EPS installation 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11

NOTE:
Coat the one-hole lug with an antioxidant compound before crimping. Also, bring any unplated mating surfaces to a
shiny finish and coat with an before mating. Plated mating surfaces must be clean and free from contamination.
NOTE:
The rack installation ears are not suitable for grounding.
To connect the ground cable to the switch:
1.
Cut your user-supplied ground cable to the wanted length. The cable length must facilitate proper operation of the fault
interrupt circuits. Use the shortest cable route allowable.
2.
Crimp the ground cable inside the preinstalled ground lug.
3.
Attach the other end of the ground cable to a suitable ground point such as the rack or cabinet.
NOTE:
Always secure the DC output cable to the output terminal block when EPS operating.
Visual display workplaces
This device is not intended for use in the direct field of view at visual display workplaces. To avoid incommoding reflexions at
visual display workplaces this device must not be placed in the direct field of view.
Bemerkung: Dieses Gerät ist nicht für den Einsatz im direkten Sichtfeld am Bildschirmarbeitsplatz vorgesehen. Um störende
Reflexionen am Bildschirmarbeitsplatz zu vermeiden, darf dieses Gerät nicht im direkten Sichtfeld platziert werden.
N-Series EPS installation
11