GE SG50T12TVT Use and Care Manual - Page 12

Venting, Blower Assembly Installation

Page 12 highlights

Operating Instructions Installation Instructions Safety Instructions Installing the water heater. Care and Cleaning The water heater must be installed with the factory supplied blower assembly in place. DANGER: Failure to install the blower assembly and properly vent the water heater to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing bodily injury, explosion, fire or death. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting section of this manual. The vent pipe must overlap a minimum of ½" on each connection. It is important that the vent pipe engages fully into any pipe fitting and be kept in that position until the adhesive has fully cured. DO NOT drill or punch holes in the plastic pipe or fittings. NOTICE: This unit is equipped with a Flammable Vapor Sensor. Do not apply power until enough time has passed to allow the vapors from the primer and cement to dissipate. Venting The water heater must be vented to the outdoors as described in these instructions. DO NOT connect this water heater to an existing vent or chimney - it must be vented separately from all other appliances. NOTICE: This unit can be vented using only the following recommended pipe material. Use only 2- or 3-inch diameter pipe. PVC (Schedule 40, ASTM D1785) CPVC (Schedule 40, ASTM F441) ABS (Schedule 40, ASTM D2661) ABS (Schedule 40 DWV, Cellular Core, ASTM F891) The fittings, other than the TERMINATION, should be equivalent to the following: PVC (Schedule 40 DWV, ASTM D2665) CPVC (Schedule 40 DWV, ASTM F438) ABS (Schedule 40 DWV, ASTM D2661) The unit may be vented horizontally through a wall or vertically through the roof. Pipe runs must be adequately supported along both vertical and horizontal runs. Maximum unsupported span is recommended to be no more than 6 feet. It is imperative that the first hanger be located on the horizontal run immediately adjacent to the first 90-degree elbow from the vertical rise. Support method used should isolate the vent pipe from floor joists or other structural members to help prevent the transmission of noise and vibration. Do not support, pin or otherwise secure the venting system in a way that restricts the normal thermal expansion and contraction of the chosen venting material. If the water heater is being installed as a replacement for an existing power vented water heater, a thorough inspection of the existing venting system must be performed prior to any installation work. Verify that the correct materials as detailed above have been used, and that the minimum or maximum vent length and terminal locations as detailed in this manual have been met. Carefully inspect the entire venting system for any signs of cracks or fractures, particularly at the joints between elbows or other fittings and the straight runs of vent pipe. Check the system for signs of sagging or other stresses in the joints as a result of misalignment of any components in the system. If any of these conditions are found, they must be corrected in accordance with the venting instructions in this manual before completing the installation and putting the water heater into service. NOTICE: The vent piping must be connected to the blower assembly using the rubber coupling and supplied clamps. The vent pipe connections at the blower assembly must be leak tested with soap and water solution upon initial startup. Repair any leaks before allowing the water heater to operate. Additional installation information for The Commonwealth of Massachusetts is located on the back page of this maunal. Blower Assembly 12 Rubber Coupling Flue Baffle Blower Assembly Installation (If not factory installed) Connect blower assembly with the electrical connector. Attach Blower Assembly to top pan using the six (6) screws provided (See diagram to the left). Install rubber coupling (supplied in the box with water heater) on blower housing and secure it. NOTICE: The Blower Assembly is Btuh input specific and is not certified for use on any other Btuh input model. Troubleshooting Tips Customer Service

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Installing the water heater.
The water heater must be installed with the factory supplied blower assembly in place.
Venting
The water heater must be vented to
the outdoors as described in these
instructions. DO NOT connect this water
heater to an existing vent or chimney - it
must be vented separately from all other
appliances.
NOTICE: This unit can be vented using only
the following recommended pipe material.
Use only 2- or 3-inch diameter pipe.
PVC (Schedule 40, ASTM D1785)
CPVC (Schedule 40, ASTM F441)
ABS (Schedule 40, ASTM D2661)
ABS (Schedule 40 DWV, Cellular Core,
ASTM F891)
The fittings, other than the TERMINATION,
should be equivalent to the following:
PVC (Schedule 40 DWV, ASTM D2665)
CPVC (Schedule 40 DWV, ASTM F438)
ABS (Schedule 40 DWV, ASTM D2661)
The unit may be vented horizontally
through a wall or vertically through the
roof.
Pipe runs must be adequately supported
along both vertical and horizontal runs.
Maximum unsupported span is
recommended to be no more than 6 feet.
It is imperative that the first hanger be
located on the horizontal run immediately
adjacent to the first 90-degree elbow
from the vertical rise.
Support method used should isolate
the vent pipe from floor joists or other
structural members to help prevent the
transmission of noise and vibration.
Do not support, pin or otherwise secure
the venting system in a way that
restricts the normal thermal expansion
and contraction of the chosen venting
material.
If the water heater is being installed as a
replacement for an existing power vented
water heater, a thorough inspection of
the existing venting system must be
performed prior to any installation work.
Verify that the correct materials as
detailed above have been used, and that
the minimum or maximum vent length
and terminal locations as detailed in this
manual have been met.
Carefully inspect the entire venting
system for any signs of cracks or
fractures, particularly at the joints
between elbows or other fittings and the
straight runs of vent pipe.
Check the system for signs of sagging or
other stresses in the joints as a result
of misalignment of any components in the
system.
If any of these conditions are found, they
must be corrected in accordance with the
venting instructions in this manual before
completing the installation and putting
the water heater into service.
NOTICE: The vent piping must be
connected to the blower assembly
using the rubber coupling and
supplied clamps. The vent pipe
connections at the blower assembly
must be leak tested with soap and
water solution upon initial startup.
Repair any leaks before allowing
the water heater to operate.
Additional installation information for
The Commonwealth of Massachusetts is
located on the back page of this maunal.
DANGER: Failure to
install the blower
assembly and properly
vent the water heater to
the outdoors as outlined
in the Venting section of
this manual will result in
unsafe operation of the
water heater causing
bodily injury, explosion,
fire or death.
To avoid the risk of
fire, explosion, or
asphyxiation from
carbon monoxide, NEVER
operate the water heater
unless it is properly
vented and has adequate
air supply for proper
operation as outlined in
the Venting section of
this manual.
The vent pipe must
overlap a minimum of ½”
on each connection.
It
is important that the vent
pipe engages fully into
any pipe fitting and be
kept in that position until
the adhesive has fully
cured.
DO NOT drill
or punch holes in the
plastic pipe or fittings.
NOTICE: This unit is
equipped with a Flammable
Vapor Sensor.
Do not apply
power until enough time
has passed to allow the
vapors from the primer and
cement to dissipate.
Blower Assembly Installation
(If not factory installed)
Connect blower assembly with the electrical connector. Attach
Blower Assembly to top pan using the six (6) screws provided
(See diagram to the left). Install rubber coupling (supplied in
the box with water heater) on blower housing and secure it.
NOTICE:
The Blower Assembly is Btuh input specific and
is not certified for use on any other Btuh input model.
12
Customer Service
Troubleshooting Tips
Care and Cleaning
Operating Instructions
Installation Instructions
Safety Instructions
Flue
Baffle
Rubber
Coupling
Blower
Assembly