GE SG50T12TVT Use and Care Manual - Page 14

Additional Considerations, Horizontal Vent Terminal Location

Page 14 highlights

Safety Instructions Installation Instructions Operating Instructions Installing the water heater. NOTICE: All pipe, fittings, solvent cement, primers and procedures must conform to American National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards. Horizontal Vent Terminal Location The location of the vent terminal depends on the following minimum clearances and considerations (see illustration): Soffit vents 4' 4' Inside corner Electric meter 18" 18" 4' window or vent 4' 4' 3' above if within 10' Fresh air intake 12" (Above grade/snow level) Vent Terminal must be at least twelve (12) inches above grade level and above normal snow levels. Vent Terminal must be at least four (4) feet below, or four (4) feet horizontally from any door, window, soffit, under eave vent or gravity air inlet to the building or other appliances, or from gas or electric meters. Do not locate vent above walkways, doors, windows, air inlets, gas or electric meters or other equipment. Vent Terminal must be at least three (3) feet above any forced air inlet located within ten (10) feet. Any fresh or make-up air inlet such as for a dryer or furnace area is considered to be a forced air inlet. Vent Terminal must be at least eighteen (18) inches from an inside corner formed by two exterior walls. Additional Considerations Caulk Rising moisture will collect under eaves If soffit vent is too close, block off and install new vent at Inside another location corner Caulk 6' (1.83 m) caulk zone (1.83 m) 6' 6' (1.83 m) caulk zone or to edge of window etc., starting within 6' (1.83 m) Caulk RTV silicone caulk Do Not install vent terminal under any patio or deck. T o help prevent moisture from freezing on walls and under eaves, do not locate vent terminal on the side of a build­ing with prevailing winter winds. D o Not terminate vent pipe directly on brick or masonry surfaces. Use a rust-resistant sheet metal backing plate (2 x 2 feet) behind vent. (See illustration.) D o Not locate vent terminal too close to shrubbery, as flue gasses may damage them. C aulk all cracks, seams and joints within six (6) feet of vent terminal. 4' (1.22 m) 2 ft. sq. (60 x 60 m) sheet metal plate on brick or masonary surface is recomended. WARNING: Moisture in the flue gas will condense as it leaves the vent terminal. In cold weather this condensate can freeze on the exterior wall, under the eaves and on surrounding objects. Some discoloration to the exterior of the building is to be expected. However, improper location or installation can result in severe damage to the structure or exterior finish of the building. A ll painted surfaces should be primed to lessen the chance of physical damage. Painted surfaces will require maintenance. Insulate vent pipe exposed to cold conditions (attics, crawl spaces, etc.) with inflammable material to help prevent moisture from accumulating in vent pipe. Do Not extend exposed vent pipe outside of building. Care and Cleaning Troubleshooting Tips Customer Service 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Additional Considerations
Do Not install vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building
with prevailing winter winds.
Do Not terminate vent pipe directly on brick or masonry
surfaces. Use a rust-resistant sheet metal backing plate
(2 x 2 feet) behind vent. (See illustration.)
Do Not locate vent terminal too close to shrubbery, as flue
gasses may damage them.
Caulk all cracks, seams and joints within six (6) feet of vent
terminal.
All painted surfaces should be primed to lessen the chance
of physical damage. Painted surfaces will require
maintenance.
Insulate vent pipe exposed to cold conditions (attics, crawl
spaces, etc.) with inflammable material to help prevent
moisture from accumulating in vent pipe.
Do Not extend exposed vent pipe outside of building.
If soffit vent is too
close, block off and
install new vent at
another location
Inside
corner
Caulk
Caulk
Caulk
6' (1.83 m)
caulk
zone or to edge of
window etc., starting
within 6'
Rising moisture will
collect under eaves
4'
(1.22 m)
6'
caulk zone
2 ft. sq. (60 x 60 m) sheet metal plate on
brick or masonary surface is recomended.
RTV silicone caulk
(1.83 m)
(1.83 m)
(1.83 m)
6'
WARNING: Moisture in the flue gas will
condense as it leaves the vent terminal. In cold
weather this condensate can freeze on the exterior
wall, under the eaves and on surrounding objects.
Some discoloration to the exterior of the building is
to be expected. However, improper location or
installation can result in severe damage to the
structure or exterior finish of the building.
Horizontal Vent Terminal Location
The location of the vent terminal depends on the following
minimum clearances and considerations (see illustration):
Vent Terminal must be at least twelve (12) inches above
grade level and above normal
snow levels.
Vent Terminal must be at least four (4) feet below, or four
(4) feet horizontally from any door, window, soffit, under
eave vent or gravity air inlet to the building or other
appliances, or from gas or electric meters. Do not locate
vent above walkways, doors,
windows, air inlets, gas or
electric meters or other equipment.
Vent Terminal must be at least three (3) feet above any
forced air inlet located within ten (10) feet. Any fresh or
make-up air inlet such as for a dryer or furnace area is
considered to be a forced air inlet.
Vent Terminal must be at least eighteen (18) inches from an
inside corner formed by two exterior walls.
4'
4'
Soffit vents
18"
4'
4'
4'
18"
Electric
meter
Inside
corner
3' above
if within 10'
Fresh
air
intake
12" (Above grade/snow level)
window or vent
14
NOTICE: All pipe, fittings, solvent cement, primers and procedures must conform to American
National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards.
Safety Instructions
Installation Instructions
Operating Instructions
Care and Cleaning
Troubleshooting Tips
Customer Service
Installing the water heater.