Trouble code

Page 47 highlights

Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA After compressor is running for 3 minutes, the unit will check the pipe pressure, when the pipe pressure is too low and low pressure switch is running for 30 senconds, compressor and outdoor fan motor will stop and will send failure 13. Trouble code The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code. Remote control indoor PCB flash times Wired controll er display Central controll er Fault description display Possible cause Remedy 10 08(08H) 21D Fault in drain Float switch is open 25m or due to the signal, system longer resumable 1 01(01H) 01D Indoor ambient sensor broken down or short due to the signal, temp. sensor failure circuit for more than 2m resumable continuously 2 02(02H) 02D Indoor pipe temp. sensor broken down or short due to the signal, sensor failure circuit for more than 2m resumable continuously 3 74(4AH) 11D Outdoor ambient sensor broken down or short due to the signal, temp. sensor failure circuit for more than 2m resumable continuously 4 73(49H) 12D Outdoor pipe temp. sensor broken down or short due to the signal, sensor failure circuit for more than 2m resumable continuously 5 72(48H) 10D Overcurrent Detector CT current is above Need to be the limit 3 times within 30m. checked, reset 6 83(53H) 14D High pressure High pressure switch acts for Need to be malfunction 3 times in 30m checked, reset 7 71(47H) 22D Power failure Wrong phase, phase Need to be failure or loss checked, reset 8 07(07H) 06D Communication communication abnormal for due to the signal, failure between more than 4m continuously resumable wired controller and indoor unit 9 06(06H) 05D Communication communication abnormal for due to the signal, failure between more than 4m continuously resumable indoor and outdoor units 11 11(0BH) 30D External alarm External alarm is cut out for due to the signal, signal input 10s or longer resumable 12 03(03H) 20D Fault in coil/suction sensor broken down or short due to the signal, line temp. sensor circuit for more than 2m resumable continuously 13 13(0DH 31D Temperature Directional valve malfunction Need to be ) shut-off repeats 3 times checked, reset 14 76(4CH 15D Fault in discharging sensor broken down or short due to the signal, ) temp. sensor circuit for more than 2m resumable continuously 15 05(05H) 17D EEPROM error EEPROM data loss Default operation 16 84(54H) 26D Low pressure low pressure switch is Need to be malfunction activated checked, reset 17 80(50H) 15D Compressor Detected temperature of Resrorable overheat discharge line is higher when lower than 120℃ than 100℃ 18 12(0CH 23D Fault in operation Indoor units operate in Resrorable in ) mode different modes same operation mode 19 75(4BH) 18D Outdoor coil sensor broken down or short due to the signal, B(suction circuit for more than 2m resumable sensor-multi) continuously 20 77(4DH 15D Outdoor sensor broken down or short due to the signal, 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63

After compressor is running for 3 minutes, the unit will check the pipe pressure, when the pipe
pressure is too low and low pressure switch is running for 30 senconds, compressor and outdoor
fan motor will stop and will send failure
13. Trouble code
The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code.
Remote
control
indoor
PCB flash
times
Wired
controll
er
display
Central
controll
er
display
Fault description
Possible cause
Remedy
10
08(08H)
21D
Fault
in
drain
system
Float switch is open 25m or
longer
due to the signal,
resumable
1
01(01H)
01D
Indoor
ambient
temp. sensor failure
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
2
02(02H)
02D
Indoor pipe temp.
sensor failure
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
3
74(4AH)
11D
Outdoor
ambient
temp. sensor failure
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
4
73(49H)
12D
Outdoor pipe temp.
sensor failure
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
5
72(48H)
10D
Overcurrent
Detector CT current is above
the limit 3 times within 30m.
Need
to
be
checked, reset
6
83(53H)
14D
High
pressure
malfunction
High pressure switch acts for
3 times in 30m
Need
to
be
checked, reset
7
71(47H)
22D
Power failure
Wrong
phase,
phase
failure or loss
Need
to
be
checked, reset
8
07(07H)
06D
Communication
failure
between
wired controller and
indoor unit
communication abnormal for
more than 4m continuously
due to the signal,
resumable
9
06(06H)
05D
Communication
failure
between
indoor and outdoor
units
communication abnormal for
more than 4m continuously
due to the signal,
resumable
11
11(0BH)
30D
External
alarm
signal input
External alarm is cut out for
10s or longer
due to the signal,
resumable
12
03(03H)
20D
Fault in coil/suction
line
temp. sensor
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
13
13(0DH
)
31D
Temperature
shut-off
Directional valve malfunction
repeats 3 times
Need
to
be
checked, reset
14
76(4CH
)
15D
Fault in discharging
temp. sensor
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
15
05(05H)
17D
EEPROM error
EEPROM data loss
Default
operation
16
84(54H)
26D
Low
pressure
malfunction
low
pressure
switch
is
activated
Need
to
be
checked, reset
17
80(50H)
15D
Compressor
overheat
Detected temperature of
discharge line is higher
than 120
Resrorable
when
lower
than 100
18
12(0CH
)
23D
Fault in operation
mode
Indoor units operate in
different modes
Resrorable
in
same o
peration
mode
19
75(4BH)
18D
Outdoor
coil
B(suction
sensor-multi)
sensor broken down or short
circuit for more than 2m
continuously
due to the signal,
resumable
20
77(4DH
15D
Outdoor
sensor broken down or short
due to the signal,
Commercial Air Conditioner
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA
47