Haier AB122ACERA Service Manual - Page 6

Piping material, Tools, Work precautions

Page 6 highlights

Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA ■Piping material 1. Use the correct refrigerant piping and materials for R410A 2. For the pipe wall thickness, see the table below: Pipe diameter Φ6.35 Φ9.52 Φ12.7 Φ15.88 Φ19.1 Pipe wall thickness 0.8 0.8 0.8 1.0 1.2 Note: Always observe and comply with the local regulations when installing the refrigerant piping. ■Tools R410A work requires a number of special tools (* symbol). Since the tools used in R22 work cannot be used for R410A, provide the tools separately. Tool name Process and application Pipe cutter Piping cutting Refrigerant piping work *Flaring tool Pipe flaring work *Torque wrench Flare nut connection Expander Expansion at pipe connection Pipe bender Pipe bending work Nitrogen gas Pipe oxidation prevention Air tightness test Welder Pipe brazing *Gauge manifold Vacuum evacuation and refrigerant Air tightness test *Charging hose charging operation check Refrigerant additional charging *Vacuum pump (with Vacuum drying adapter) Electronic scale Refrigerant additional Gas leakage detector Gas leakage test ■Work precautions charging Refrigerant check: Before work, check the used refrigerant and prepare materials matched to the refrigerant. Refrigerant piping: Observe the basics of refrigerant piping to avoid the unnecessary problems. In addition, when performing the welding work, seal in the nitrogen gas to the pipes, and prevent it from the oxidation. Leak pressure detection: Perform seal detection and make sure there is no refrigerant leakage. Vacuum drying: If the vacuum pump has not the reverse flow check mechanism, use the pump together with a reverse flow check adapter. Additional refrigerant: Charge a suitable amount of refrigerant with a special R410A gauge manifold and charging hose. 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63

Commercial Air Conditioner
6
Piping material
1.
Use the correct refrigerant piping and materials for R410A
2.
For the pipe wall thickness, see the table below:
Pipe diameter
Φ
6.35
Φ
9.52
Φ12.7
Φ15.88
Φ19.1
Pipe wall thickness
0.8
0.8
0.8
1.0
1.2
Note: Always observe and comply with the local regulations when installing the refrigerant piping.
Tools
R410A work requires a number of special tools (* symbol). Since the tools used in R22 work
cannot be used for R410A, provide the tools separately.
Tool name
Process and application
Pipe cutter
Piping cutting
*Flaring tool
Pipe flaring work
*Torque wrench
Flare nut connection
Expander
Expansion at pipe connection
Pipe bender
Pipe bending work
Refrigerant piping work
Nitrogen gas
Pipe oxidation prevention
Welder
Pipe brazing
Air tightness test
*Gauge manifold
*Charging hose
Vacuum
evacuation
and
refrigerant
charging operation check
Air tightness test
Refrigerant
additional
charging
*Vacuum
pump
(with
adapter)
Vacuum drying
Electronic scale
Gas leakage detector
Gas leakage test
Refrigerant
additional
charging
Work precautions
Refrigerant check:
Before work, check the used refrigerant and prepare materials matched to the
refrigerant.
Refrigerant piping:
Observe the basics of refrigerant piping to avoid the unnecessary problems. In
addition, when performing the welding work, seal in the nitrogen gas to the pipes, and prevent it
from the oxidation.
Leak pressure detection:
Perform seal detection and make sure there is no refrigerant leakage.
Vacuum drying:
If the vacuum pump has not the reverse flow check mechanism, use the pump
together with a reverse flow check adapter.
Additional refrigerant:
Charge a suitable amount of refrigerant with a special R410A gauge
manifold and charging hose.
Model: AU122AEERA AB122ACERA
AC122ACERA AD122ALERA