HP DL360 hp ProLiant DL360 generation 3 server high-density deployment
HP DL360 - ProLiant - G3 Manual
UPC - 613326948835
View all HP DL360 manuals
Add to My Manuals
Save this manual to your list of manuals |
HP DL360 manual content summary:
- HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 1
2 Executive Summary 2 Glossary 3 ProLiant DL360 G3 Server Power Requirements 5 Power Distribution Solutions 6 Modular PDU 6 Power/Jumper Cords 8 Console Management Systems 8 In-Rack Local Consoles 8 Planning Rack Configurations 8 Weight Considerations 8 Special Considerations - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 2
are loaded on multiple machines creating the need to fit a large number of density-optimized servers into existing server rooms and data centers. HP meets this need with the density-optimized line of HP ProLiant servers, such as the ProLiant DL360 G3 server. At a height of 1U each, up to 42 of these - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 3
HP ProLiant DL360 G3 Server used in North America, Latin America, and Japan. Power Density The amount (product) of amps and voltage provided to a system (VA). A 120-VAC delivered to it. The rating is expressed as either a decimal number between 0 and 1 or percentage of the formula of dividing watts - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 4
HP ProLiant DL360 G3 Server High-Density Deployment Table 1. Glossary of Power Terms I = current in amperes. In three-phase systems VA = 1.73 × E × I. A rating of true power consumed by the product and measured with an input power meter. In single-phase systems W = E x I x pf, where E = volts, I - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 5
HP and listed later in this document. The ProLiant DL360 G3 server power specifications are provided in the following table using values derived from the product specification as well as the Power Calculator utility with a server in nominal and maximum configurations. Table 2. ProLiant DL360 G3 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 6
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Power Distribution Solutions HP recommends using power distribution units (PDUs) in installations where a number of server units can place serious loading demands on the AC power bus. HP offers PDUs that provide safety and - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 7
HP ProLiant DL360 G3 Server High-Density Deployment Figure 3. Modular PDU Components Control Core Preliminary Extension Bar (2 of 4) Shown with Double-Bar Brackets Table 3. Modular PDU types Name, PN Voltage / - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 8
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Power/Jumper Cords Although PDUs and servers are typically shipped with power cords, the physical and/or electrical requirements for a particular configuration may require different cords. WARNING: Never cut or splice cords to - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 9
HP ProLiant DL360 G3 Server High-Density Deployment Table 4. Local/IP Console Management Options Preliminary Product Name HP Part No. 4Interface Adapters (8 per Pack) 262587B21 Interface Adapters (Single Pack) Expansion Module CAT5 Cables 3FT (4 per Pack) CAT5 Cables 6FT (8 per Pack) CAT5 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 10
density per console switch. Table 5 outlines the number of devices that fully populate a 47U, 42U, or 36U rack with an in-rack local console. Table 5. Device Configuration for an In-Rack Local IP Console Device or Cable 47U Rack ProLiant DL360/320 G3 servers 46 KVM IP Console Switches Interface - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 11
HP ProLiant DL360 G3 Server High-Density Deployment Figure 4. Remote Console Management System Preliminary 11 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 12
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Planning Rack Configurations You must consider several important factors when planning a rack configuration: • The number of servers deployed in the rack • The number of other devices such as keyboard drawers, video displays, and - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 13
and Installation Guide for complete installation instructions. Telco Rack Solution Many data centers use two post telecommunication (telco) racks. The ProLiant DL360 G3 server design supports deployment in telco racks. HP offers a telco rack kit designed to install ProLiant DL360 G3 servers in - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 14
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Online Calculators HP provides online calculator DL360 G3 server. Using drop-down menus, the user selects the number of CPUs, memory amount, hard drive type and amount, and PCI card compliment of the server. Each configuration - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 15
HP ProLiant DL360 G3 Server High-Density Deployment Figure 5. Opening Screen Of Power Calculator Utility Preliminary The power calculator is convenient for small server system planning or for making minor additions to existing installations. For a more thorough analysis of a complete installation - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 16
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Rack/Site Preparation Utility The Rack/Site Installation Preparation Utility will calculate all power, vertical rack space, and air flow requirements for a complete server installation. In addition, the Rack/Site Installation - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 17
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary To use the Rack/Site Installation all appropriate parameters are chosen. Be aware of error messages indicating possible problems. 2. When component configuration is complete, click on the Rack Site Installation tab to return to - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 18
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Power Configurations Examples Suggested Configurations The high/low voltage and dual-power supply capabilities of the ProLiant DL360 G3 server makes it adaptable to a variety of power configurations. Each of the following examples - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 19
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Configuration A: Maximum Performance Density (42 servers, high-voltage) Single or Dual Power Supply This configuration shows a "best practice" for a 42U rack with 42 servers in a high-voltage configuration summary (Table 7). Table - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 20
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Figure 8. Configuration A (Maximum Performance Density) Power Cabling Diagram (42 ProLiant DL360 G3 Servers with Redundant Power Supplies) Note: S1A= server 1 with power supply A and S1B= Server 1 with power supply B 20 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 21
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary One 40A Modular PDU connects to power feeds A and B to support 21 ProLiant DL360 G3 servers with redundant power supplies. Figure 9. Configuration A (Maximum Performance Density) Ethernet Cable Diagram Switches in Another Rack 64x - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 22
HP ProLiant DL360 G3 Server High-Density Deployment Configuration B: Maximum Flexibility (35 servers, high-voltage) Table 8. Configuration B Summary Preliminary Configuration B Summary Rack Contents Units 35 Servers the maximum number of outlets to be mounted on the same side of the rack - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 23
HP ProLiant DL360 G3 Server High-Density Deployment Figure 10. Configuration B (Maximum Flexibility) Power Cabling Diagram Preliminary Note: S1A= server 1 with power supply A and S1B= Server 1 with power supply B One 40A Modular PDU connects to power feeds A and B to support 17 or 18 ProLiant - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 24
HP ProLiant DL360 G3 Server High-Density Deployment Figure 11. Configuration B (Maximum Flexibility) KVM Switch Cabling Diagram Preliminary 24 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 25
HP ProLiant DL360 G3 Server High-Density Deployment Figure 12. Configuration B (Maximum Flexibility) Ethernet Cable Diagram Preliminary 25 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 26
HP ProLiant DL360 G3 Server High-Density Deployment Configuration C: Traditionalist 24 servers, low-voltage Table 9. Configuration C Summary Preliminary Configuration C Summary Rack Contents Units 24 Servers with all fixed or all sliding rails with cable trays 4 Low-voltage 24 A 0U/1U PDUs 2 x - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 27
HP ProLiant DL360 G3 Server High-Density Deployment Figure 13. Configuration C (Traditionalist) Power Connections Preliminary Note: S1A= server 1 (single Power Supply); 24 24PH= 24 Port Ethernet Hub; 48PS= 48 Port Ethernet Switch; IPCS= IP Console Switch; TFT= TFT5600 1U Keyboard/Monitor 27 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 28
HP ProLiant DL360 G3 Server High-Density Deployment Figure 14. Configuration C (Traditionalist) Ethernet Cable Preliminary 28 x FE 14 x FE 14 x FE 84 x Cat 5 Cables Routed Inside Server Cabinet Switches on top of Rack 8x GbE + 4x FE Uplink to Network Backbone 2x FE 24 Port Hub (24 FE) 1 6 x - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 29
HP ProLiant DL360 G3 Server High-Density Deployment Figure 15. Configuration C (Traditionalist) KVM Switch Cabling Diagram Preliminary 29 - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 30
HP ProLiant DL360 G3 Server High-Density Deployment Preliminary Conclusion Completing the Installation The load requirements of high-density server installations can be significant. Careful planning using accurate calculations and providing overhead compensation for peripheral devices can greatly - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 31
ProLiant DL360 G3 server orms/index.html Specifications, options, and a list of other HP products and options compatible with the ProLiant DL360 G3 server HP ProLiant DL360 Generation 3 QuickSpecs Installation and service guidelines for the ProLiant DL360 G3 server www.compaq.com/support/servers - HP DL360 | hp ProLiant DL360 generation 3 server high-density deployment - Page 32
HP ProLiant DL360 G3 Server High-Density Deployment For More Information Product information: 1-325-345-1518 Pre-sales: 1-325-282-6672 Preliminary Post-sales: 1-325-652-6672 Business partner sales consulting: 1-325-888-5874 For more information on ProLiant servers visit www.hp.com/servers/
HP ProLiant DL360 Generation 3 Server High-Density
Deployment
Table of Contents
Introduction
2
Symbols in Text
2
Executive Summary
2
Glossary
3
ProLiant DL360 G3 Server Power Requirements
5
Power Distribution Solutions
6
Modular PDU
6
Power/Jumper Cords
8
Console Management Systems
8
In-Rack Local Consoles
8
Planning Rack Configurations
8
Weight Considerations
8
Special Considerations For Compaq Branded Racks
8
Rack Management Systems
8
Universal Rack Rails
8
Sliding Rack Rails
8
Telco Rack Solution
8
Online Calculators
8
Power Calculator Utility
8
Rack/Site Preparation Utility
8
To use the Rack/Site Installation Preparation Utility
8
Power Configurations Examples
8
Suggested Configurations
8
Configuration A:
Maximum Performance Density
8
Configuration B: Maximum Flexibility
8
Configuration C: Traditionalist
8
Conclusion
8
Completing the Installation
8
Reference Information and Glossary
8
For More Information
8
Feedback
8
HP Industry
Standard Servers
July 2003
White Paper
[Document No.
5982-0394EN]