HP DL360 hp ProLiant DL360 generation 3 server high-density deployment - Page 7

Name, PN, Voltage, Amperage, AC Bus, Plug Type, Extension Bar, Output Receptacle, Type Qty

Page 7 highlights

HP ProLiant DL360 G3 Server High-Density Deployment Figure 3. Modular PDU Components Control Core Preliminary Extension Bar (2 of 4) Shown with Double-Bar Brackets Table 3. Modular PDU types Name, PN Voltage / Amperage 24A NA/JPN Low, 252663-D71 24A NA/JPN High, 252663-D72 32A International, 252663- B31 40A World Wide, 252663- B21 100-127/ 24 200-240 / 24 200-240 / 32 200-240 / 40 AC Bus Plug Type NEMA L5-30P NEMA L6-30P IEC 309 32A Terminals for hardwiring Extension Bar Output Receptacle Type (Qty) 4 x NEMA 5-15R (8) 4 x IEC 320 C13 (8) 4 x IEC 320 C13 (8) 3 x IEC 320 C13 (8) 1 x IEC 320 C19 (4) 16A World Wide 200-240 / 16 252663- B24 1 x IEC 320 C20 (1) 1 x IEC 320 C19 (2) 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

HP ProLiant DL360 G3 Server High-Density Deployment
Preliminary
7
Figure 3.
Modular PDU Components
Control Core
Extension Bar (2 of 4)
Shown with Double-Bar Brackets
Table 3.
Modular PDU types
Name, PN
Voltage /
Amperage
AC Bus
Plug Type
Extension Bar
Output Receptacle
Type (Qty)
24A NA/JPN
Low,
252663-D71
100-127/ 24
NEMA L5-30P
4 x NEMA 5-15R (8)
24A NA/JPN
High,
252663-D72
200-240 / 24
NEMA L6-30P
4 x IEC 320 C13 (8)
32A
International,
252663-B31
200-240 / 32
IEC 309 32A
4 x IEC 320 C13 (8)
40A World
Wide,
252663-B21
200-240 / 40
Terminals for
hardwiring
3 x IEC 320 C13 (8)
1 x IEC 320 C19 (4)
16A World Wide
252663-B24
200-240 / 16
1 x IEC 320 C20
(1)
1 x IEC 320 C19 (2)