HP DL360 hp ProLiant DL360 generation 3 server high-density deployment - Page 5

ProLiant DL360, G3 Server Power, Requirements - proliant g3 standard watts

Page 5 highlights

HP ProLiant DL360 G3 Server High-Density Deployment Preliminary ProLiant DL360 G3 Server Power Requirements In the standard single-processor configuration, the ProLiant DL360 G3 server includes one 325-watt power supply that can operate off high or low voltage AC power. Single power supply units can be upgraded to a dual-power supply configuration with a redundant power supply option kit. The power supplies are hot-pluggable, allowing live removal and replacement. The ProLiant DL360 G3 server uses an IEC C14-type AC plug that requires a power cable with an IEC C13 receptacle at one end. Power cord kits that are compatible with the physical and electrical requirements of the DL360 G3 server are available from HP and listed later in this document. The ProLiant DL360 G3 server power specifications are provided in the following table using values derived from the product specification as well as the Power Calculator utility with a server in nominal and maximum configurations. Table 2. ProLiant DL360 G3 Server Power Specifications Input Voltage Power Supply Rated Output (W) Nom. Input Wattage (W) Max. Input Wattage (W) Nom. Input Current Draw (A) 100 325 234 338 2.4 115 325 232 336 2.1 208 325 227 329 1.1 220 325 224 326 1.0 230 325 222 324 1.0 240 325 220 321 0.9 Max. Input Current Draw (A) 3.5 3.0 1.6 1.5 1.4 1.4 Nom. Input (Va) 238 237 231 228 227 225 Max. Input (Va) Max. Thermal (Btu/Hr) Efficiency (%) Power Factor 345 1154 72.1 0.98 343 1146 72.6 0.98 336 1123 74.1 0.98 332 1111 74.9 0.98 330 1104 75.4 0.98 328 1095 76.0 0.98 Nom. Leakage Current (Ma) Max. Leakage Current (Ma) 0.31 0.63 0.36 0.72 0.65 1.30 0.69 1.38 0.72 1.44 0.75 1.50 Nom Inrush Current (A) @ 2 30 30 30 30 30 30 Ms Max Inrush Current (A) @ 2 Ms 60 60 60 60 60 60 NOTES: Nom. = Nominal rating of a unit operating w/ one processor, 1HDD, up to 2 DIMMs, and no PCI cards. Max. = Maximum rating of a fully loaded unit: 2 processors, 2HDD, 4 DIMMs, 1 PCI cards, and 2 power supplies. These values are derived from a combination of product specifications and the Power Calculator configured as above in "Nom" and "Max." 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32

HP ProLiant DL360 G3 Server High-Density Deployment
Preliminary
5
ProLiant DL360
G3 Server Power
Requirements
In the standard single-processor configuration, the ProLiant DL360 G3 server includes
one 325-watt power supply that can operate off high or low voltage AC power. Single
power supply units can be upgraded to a dual-power supply configuration with a
redundant power supply option kit. The power supplies are hot-pluggable, allowing live
removal and replacement.
The ProLiant DL360 G3 server uses an IEC C14-type AC plug that requires a power
cable with an IEC C13 receptacle at one end.
Power cord kits that are compatible with
the physical and electrical requirements of the DL360 G3 server are available from HP
and listed later in this document.
The ProLiant DL360 G3 server power specifications are provided in the following table
using values derived from the product specification as well as the
Power Calculator
utility
with a server in nominal and maximum configurations.
Table 2.
ProLiant DL360 G3 Server Power Specifications
Input Voltage
100
115
208
220
230
240
Power Supply Rated Output
(W)
325
325
325
325
325
325
Nom. Input Wattage (W)
234
232
227
224
222
220
Max. Input Wattage (W)
338
336
329
326
324
321
Nom. Input Current Draw (A)
2.4
2.1
1.1
1.0
1.0
0.9
Max. Input Current Draw (A)
3.5
3.0
1.6
1.5
1.4
1.4
Nom. Input (Va)
238
237
231
228
227
225
Max. Input (Va)
345
343
336
332
330
328
Max. Thermal (Btu/Hr)
1154
1146
1123
1111
1104
1095
Efficiency (%)
72.1
72.6
74.1
74.9
75.4
76.0
Power Factor
0.98
0.98
0.98
0.98
0.98
0.98
Nom. Leakage Current (Ma)
0.31
0.36
0.65
0.69
0.72
0.75
Max. Leakage Current (Ma)
0.63
0.72
1.30
1.38
1.44
1.50
Nom Inrush Current (A) @ 2
Ms
30
30
30
30
30
30
Max Inrush Current (A) @ 2
Ms
60
60
60
60
60
60
NOTES:
Nom. = Nominal rating of a unit operating w/ one processor, 1HDD, up to 2
DIMMs, and no PCI cards.
Max. = Maximum rating of a fully loaded unit: 2 processors, 2HDD, 4 DIMMs, 1 PCI
cards, and 2 power supplies.
These values are derived from a combination of product specifications and the Power