HP Scitex LX600 HP Scitex LX Printer Family - Site preparation guide - Page 12
WARNING, Power cables LX600
View all HP Scitex LX600 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 12 highlights
Site preparation Table 2-7 LX800 single-phase circuit breaker specifications (continued) High-voltage systems Low-voltage systems Input frequency 50 Hz 60 Hz Single-phase branch circuit breaker 2 poles, 16/20 A 2 poles, 16/20 A WARNING! Ensure that the printer's built-in three-phase circuit breaker or ground fault circuit interruptor operates in the case of a current leakage fault to the product chassis, even when an isolation device (such as an isolating transformer) will be used to supply power to the printer. WARNING! Ensure that mains fault current is adequate for proper operation of the supplementary circuit breakers incorporated in the printer (10 kA rated interrupting capacity). Power cables (LX600) Two power cables are provided with the LX600 printer, and each is 5 m (16 ft) long. If those cables do not reach your PDU and/or UPS, a certified electrician must install suitable extension cables on the day of installation. The cables must meet the following minimum specifications: Table 2-8 Cable specifications Three-phase line Single-phase line Configuration Wire 4 wires, L1/L2/L3/PE Strained Cu, AWG8, 10 mm² 3 wires, L/N/PE Strained Cu, AWG12, 4 mm² Power cables (LX800) A three-phase power cable is not provided with the LX800 printer. The cables that you use must meet the following minimum specifications. Table 2-9 Cable specifications Three-phase line Configuration 4 wires, L1/L2/L3/PE Wire Strained Cu, AWG6, 13 mm² Maximum external diameter 30 mm (1.18 in) PE connections should be made through an M6 stub. 8 Chapter 2 Site preparation Single-phase line 3 wires, L/N/PE Strained Cu, AWG12, 4 mm² - ENWW