LG L1404R Service Manual - Page 30

IC01M DC 12V?

Page 30 highlights

Troubleshooting Guide Possible Trouble 2 The compressor does not operate. Is desired Temp. set lower than Room NO Temp.-0.5°C? YES • Select the desired Temp. to lower Number. Is the voltage No.10 NO of IC01M 0V? Is the voltage N0.9 of NO NO Is the Unit for 3 minutes IC01M DC 12V? delay? YES • Check the RY-COMP. • Check the wiring Diagram. YES • Replace IC01M. YES • Wait 3 Minutes. • Replace AC PCB Ass'y. Possible Trouble 3 The compressor always operate. Is the wire connection of NO RY-COMP OK? YES • Check the RY-COMP. • Connect LEAD Wire to RY-COMP again. 30 Room Air Conditioner