Panasonic 26PEK1U6 Tech Data - Service Manual - Page 134

Cold Draft Prevention (Heating Cycle), Processes and functions

Page 134 highlights

2. Processes and functions 2-2 Cold Draft Prevention (Heating Cycle) The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF. This condition occurs in the following 3 cases: • During Thermo OFF (refer to 2-1 B. Room Temperature Control, Heating) • During the defrosting operation (refer to 2-10 Defrosting Control, Heating) • Until either the coil temperature E2 reaches 81°F or when a maximum of 6 minutes has past. The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give the fan an initial boost. 92 88 INDOOR UNIT COIL TEMP. E2 (°F) 81 MAX. 6 MINUTES 2 77 50 SET AUTO OR H LL LL/OFF LL FAN SPEED M LL LL/OFF LL L LL LL/OFF LL "STANDBY" INDICATOR "STANDBY" APPEARS LL= Very low speed L= Low speed L M H L M M L L L M= Medium speed H= High speed 1135_THS_I Fig. 3 Chart Summary and Explanations The main idea of this chart is to show that the indoor fan speed increases and gets closer to the set fan speed as the coil temperature E2 rises. The indoor unit fs coil temperature is taken from sensor E2 located in the middle of the indoor heat exchange coil. The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2 falls below 50 ˚F, the indoor fan motor stops running. 2-4

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198

2-4
2. Processes and functions
Fig. 3
92
88
81
77
50
SET
FAN
SPEED
AUTO
OR
H
M
L
LL
LL/OFF
LL
L
L
L
LL
LL/OFF
LL
L
M
M
LL
LL/OFF
LL
L
M
H
MAX.
6
MINUTES
“STANDBY”
INDICATOR
INDOOR
UNIT
COIL TEMP.
E2 (
°
F)
LL= Very low speed
L= Low speed
M= Medium speed
H= High speed
“STANDBY” APPEARS
1135_THS_I
Chart Summary and Explanations
The main idea of this chart is to show that the indoor fan speed increases and gets closer to
the set fan speed as the coil temperature
E2
rises.
The indoor unit fs coil temperature is taken from sensor
E2
located in the middle of the indoor
heat exchange coil.
The dotted line shows that the indoor fan motor is
OFF
.
When the temperature at sensor
E2
falls below 50 ˚F, the indoor fan motor stops running.
2-2
Cold Draft Prevention (Heating Cycle)
The cold draft prevention function controls indoor fan speed so a strong draft of cold air will
not blow out before the indoor heat exchange coils have warmed up.
STANDBY shows on the remote controller when the indoor fan speed is LL (very low)
or OFF. This condition occurs in the following 3 cases:
During Thermo OFF (refer to 2-1 B. Room Temperature Control, Heating)
• During the defrosting operation (refer to 2-10 Defrosting Control, Heating)
• Until either the coil temperature E2 reaches 81°F or when a maximum of 6 minutes
has past.
The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give the
fan an initial boost.
2