Panasonic 26PEK1U6 Tech Data - Service Manual - Page 82

Specifications, HOW TO INSTALL THE INDOOR UNIT, Way Cassette Type, U1 Type

Page 82 highlights

6. HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette Type (U1 Type) 6-1. Suspending the Indoor Unit This unit uses a drain pump. Use a level gauge to check that the unit is level. 6-2. Preparation for Suspending (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs. 1-12 and 1-13), by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely and safely suspended. (2) Follow Fig. 1-13 and Table 1-4 to make the holes in the ceiling. 1 Table 1-4 Unit: inch (mm) Type Length A B S-26PU1U6 (CZ-24KPU1U) 32-9/32 (820) 22-9/32 (566) S-36PU1U6, S-42PU1U6 (CZ-36KPU1U) 43-11/16 33-11/16 (1,110) (856) (3) Determine the pitch of the suspension bolts using the supplied full-scale installation diagram. The diagram and table (Fig. 1-14 and Table 1-5) show the relationship between the positions of the suspension fitting, the unit, and the panel. 1. Specifications Hole-in-anchor Hole-in-plug Concrete Insert Suspension bolt (M10 or 3/8") (field supply) Fig. 1-12 X A (Ceiling opening) B (Suspension bolt pitch) Grille center Drain hose side 32-9/32 (Ceiling opening) 29-13/16 (Suspension bolt pitch) Fig. 1-13 Refrigerant tubing side Unit: inch Refrigerant tubing joint (gas tube side) Suspension lug Drain connection (other side) (VP25) Refrigerant tubing joint (liquid tube side) E A B C D 1-3/16 Table 1-5 Type Length S-26PU1U6 (CZ-24KPU1U) S-36PU1U6, S-42PU1U6 (CZ-36KPU1U) A 6-3/16 (157) 6-3/16 (157) Fig. 1-14 B 7-5/32 (182) 7-5/32 (182) C 10-9/32 (261) 11-15/32 (291) Unit: inch (mm) D 12-1/8 (308) E 4-7/8 (124) 13-1/16 (338) 4-7/8 (124) 1-76 Unit: inch

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198

1-76
1. Specifications
6. HOW TO INSTALL THE INDOOR UNIT
4-Way Cassette Type
(U1 Type)
6-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a level gauge to
check that the unit is level.
6-2. Preparation for Suspending
(1)
Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs. 1-12
and 1-13), by attaching them to the ceiling support
structure, or by any other method that ensures that
the unit will be securely and safely suspended.
(2)
Follow Fig. 1-13 and Table 1-4 to make the holes in
the ceiling.
(3)
Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 1-14 and Table 1-5) show the
relationship between the positions of the suspen-
sion fitting, the unit, and the panel.
Type
Length
Table 1-5
Unit: inch (mm)
S-26PU1U6
(CZ-24KPU1U)
S-36PU1U6, S-42PU1U6
(CZ-36KPU1U)
A
6-3/16
(157)
6-3/16
(157)
7-5/32
(182)
7-5/32
(182)
10-9/32
(261)
11-15/32
(291)
12-1/8
(308)
13-1/16
(338)
4-7/8
(124)
4-7/8
(124)
D
E
B
C
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 1-12
)
g
n
i
n
e
p
o
g
n
i
l
i
e
C
(
2
3
/
9
-
2
3
Grille center
nsion bolt pitch)
e
p
s
u
S
(
6
1
/
3
1
-
9
2
X
Refrigerant
tubing side
Drain hose
side
B
(Suspension bolt pitch)
A (Ceiling opening)
Fig. 1-13
C
D
6
1
/
3
-
1
B
A
E
Suspension lug
Refrigerant tubing joint (gas tube side)
Refrigerant tubing joint
(liquid tube side)
Drain connection (other side)
(VP25)
Length
Type
Table 1-4
Unit: inch (mm)
S-26PU1U6
(CZ-24KPU1U)
S-36PU1U6, S-42PU1U6
(CZ-36KPU1U)
A
32-9/32
(820)
43-11/16
(1,110)
22-9/32
(566)
33-11/16
(856)
B
Unit: inch
Fig. 1-14
Unit: inch
1