Panasonic 26PEK1U6 Tech Data - Service Manual - Page 69

Installation Instructions, Table 1-3 List of Connection Tube Sizes

Page 69 highlights

1-12. Installation Instructions Outdoor Unit 1. Tubing Size Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2. 1. Specifications Single Main tubing L H1 Table 1-1 Indoor unit type 26, 36 types 42 type Maximum length 165 ft. 165 ft. Charge-less tubing length (actual length) 10 - 100 ft. 15 - 100 ft. Additional charge per 1 ft. 0.43 oz. 1 Maximum indoor-outdoor If outdoor unit is higher H1 100 height difference If outdoor unit is lower H1 50 Table 1-2 Tubing Data for Models Tubing Data Models U-26PE1U6 U-26PS1U6 U-36PE1U6 U-36PS1U6 Tubing size outer diameter Liquid tube Gas tube in. (mm) in. (mm) 3/8 (9.52) 5/8 (15.88) 3/8 (9.52) 5/8 (15.88) Limit of tubing length (ft.) 165 165 Outdoor unit is placed Limit of elevation higher. 100 (ft.) 100 difference between the 2 units Outdoor unit is placed 50 50 lower. (ft.) Max. allowable tubing length at shipment (ft.) 10 - 100 10 - 100 Required additional refrigerant * 1 (oz./ft.) a) 0.43 b) 0.43 Refrigerant charged at shipment (lbs.) 4.2 6.2 No additional charge of compressor oil is necessary. * 1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft. Table 1-3 List of Connection Tube Sizes Main tubing (L) Type capacity of indoor units Gas tube Liquid tube Amount of additional charge per 1 ft. 26 - 42 ø5/8" ø3/8" 0.43 oz. U-42PE1U6 U-42PS1U6 3/8 (9.52) 5/8 (15.88) 165 100 50 10 - 100 b) 0.43 7.9 1-63

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198

1-63
1. Specifications
1-12.
Installation Instructions
1. Tubing Size
Outdoor Unit
Single type
Refrigerant tubing between the indoor and outdoor units
should be kept as short as possible.
The length of the refrigerant tubes between the indoor
and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make both
the tubing length (L) and the difference in elevation (H1)
as short as possible. Refer to Table 1-2.
Table 1-1
Indoor unit type
26, 36 types
42 type
165 ft.
165 ft.
Maximum length
Charge-less tubing length (actual length)
10 – 100 ft.
15 – 100 ft.
0.43 oz.
Additional charge per 1 ft.
Maximum indoor-outdoor
height difference
If outdoor unit is higher
H1
H1
100
If outdoor unit is lower
50
Single
Main tubing L
H1
Table 1-2 Tubing Data for Models
U-26PE1U6
U-26PS1U6
U-36PE1U6
U-36PS1U6
U-42PE1U6
U-42PS1U6
Tubing size
outer diameter
Liquid tube
in. (mm)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Gas tube
in. (mm)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
165
165
165
(ft.)
(ft.)
(ft.)
(ft.)
Limit of tubing length
Limit of elevation
difference between
the 2 units
Outdoor unit is placed
100
100
100
higher.
Outdoor unit is placed
50
50
50
lower.
Max. allowable tubing length at shipment
10 – 100
10 – 100
10 – 100
Required additional refrigerant *
1
(oz./ft.)
a) 0.43
b) 0.43
b) 0.43
Refrigerant charged at shipment
(lbs.)
4.2
6.2
7.9
No additional charge of compressor oil is necessary.
*
1
If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.
Table 1-3 List of Connection Tube Sizes
Main tubing (L)
Type capacity of indoor units
26 – 42
Gas tube
ø5/8"
Liquid tube
ø3/8"
Amount of additional charge per 1 ft.
0.43 oz.
Tubing Data
Models
1