Panasonic 26PEU1U6 Installation Instructions - Page 57

E 0 1, E 0 2, E 0 9, E 1 4, E 0 4, E 0 6, E 1 5, E 1 6, E 2 0, P 0 5, L 0 2, P 0 9, L 0 7, L 1 3

Page 57 highlights

57 1BOBTPOJD@1"$J@*OEPPS6OJU@64MF 5-24. Diagnosis Table Wired remote Indoor unit spcontroller dilay receiver lamp 1:1 connection (single type) Group connection Cause Simultaneous-operation multi system (flexible combination) Nothing is displayed Nothing is displayed ٨Remote controller is not connected correctly. ٨ Remote controller is not connected with ٨ Same as at left ٨ Indoor unit power is not ON. indoor unit correctly ٨ Indoor unit power is not ON. E 0 1 displayed Operating lamp E 0 2 displayed is blinking. ٨ Automatic address setting has not been completed. ٨ Inter-unit control wiring is cut or is not connected correctly. ٨ Remote controller is not connected correctly (remote controller receiving failure). ٨ Automatic address setting has not been ٨ Same as at left completed. ٨ Inter-unit control wiring is cut or is not connected correctly. ٨ Remote controller is not connected with indoor unit correctly ٨Remote controller is not connected correctly ٨ Remote controller is not connected with ٨ Same as at left (failure in transmission from remote controller indoor unit correctly to indoor unit). E 0 9 displayed E 1 4 displayed E 0 4 displayed ٨ Indoor-outdoor inter-unit wiring is not connected correctly. ٨ Same as at left ٨ Control wiring for group control is cut or is not connected correctly. ٨ Same as at left Control by main-sub remote controllers ٨ Same as at left ٨ Same as at left ٨ Same as at left ٨ 2 remote controllers are set as the main remote controller. ٨ Same as at left ٨ Same as at left E 0 6 displayed Standby lamp is blinking. E 1 5 displayed ٨ Indoor unit capacity is too low. ٨Indoor-outdoor inter-unit wiring is cut or ٨ Same as at left is not connected correctly. ٨ Same as at left ٨ Same as at left ٨ Same as at left ٨Same as at left E 1 6 displayed ٨ Indoor unit capacity is too high. E 2 0 displayed P 0 5 displayed L 0 2 displayed L 1 3 displayed L 0 7 displayed P 0 9 displayed ٨ No serial signal is being received at all from the indoor units. Operation lamp and ٨ Inter-unit circuit or open phase in the outdoor Standby lamp are unit power blinking alternately. ٨ Insufficient gas Both the Operation ٨ Indoor-outdoor unit type mismatch lamp and Standby lamp are blinking together. Timer lamp and ٨ The indoor unit ceiling panel connector is not Standby lamp are connected correctly. blinking alternately. ٨ Reversed phase or open phase in the 3-phase power at one of the outdoor units in the group ٨ Same as at left ٨ Ceiling panel connector at one of the indoor units in the group is not connected correctly. ٨ Reversed phase or open phase in the outdoor unit 3-phase power ٨ Same as at left ٨ Same as at left ٨ Control wiring for group control is connected ٨ Same as at left to the indoor unit, however it is set for individual operation. ٨ Indoor unit ceiling panel connector is not ٨ Same as at left connected correctly.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

57
5-24.
Diagnosis Table
Wired remote
Cause
E 0 1
E 0 2
E 0 9
E 1 4
E 0 4
E 0 6
E 1 5
E 1 6
E 2 0
P 0 5
L 0 2
P 0 9
displayed
L 0 7
displayed
Indoor unit
1:1 connection (single type)
Nothing is
displayed
Nothing is
displayed
displayed
displayed
Operating lamp
is blinking.
displayed
displayed
displayed
displayed
displayed
displayed
displayed
displayed
displayed
displayed
L 1 3
Standby lamp
is blinking.
Operation lamp and
Standby lamp are
blinking alternately.
Both the Operation
lamp and Standby
lamp are blinking
together.
Timer lamp and
Standby lamp are
blinking alternately.
Remote controller is not connected correctly.
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected correctly
(remote controller receiving failure).
Remote controller is not connected correctly
(failure in transmission from remote controller
to indoor unit).
Indoor-outdoor inter-unit wiring is not
connected correctly.
Indoor unit capacity is too low.
Indoor unit capacity is too high.
No serial signal is being received at all from
the indoor units.
Inter-unit circuit or open phase in the outdoor
unit power
Insufficient gas
Indoor-outdoor unit type mismatch
The indoor unit ceiling panel connector is not
connected correctly.
Group connection
Remote controller is not connected with
indoor unit correctly
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected with
indoor unit correctly
Remote controller is not connected with
indoor unit correctly
Same as at left
Indoor-outdoor inter-unit wiring is cut or
is not connected correctly.
Same as at left
Reversed phase or open phase in the
3-phase power at one of the outdoor
units in the group
Same as at left
Ceiling panel connector at one of the
indoor units in the group is not
connected correctly.
Simultaneous-operation multi system
(flexible combination)
Same as at left
Same as at left
Same as at left
Control wiring for group control is cut or
is not connected correctly.
Same as at left
Same as at left
Same as at left
Reversed phase or open phase in the
outdoor unit 3-phase power
Same as at left
Control wiring for group control
is connected
to the indoor unit, however it is set for individual
operation.
Indoor unit ceiling panel connector is not
connected correctly.
Control by main-sub
remote controllers
Same as at left
Same as at left
Same as at left
2 remote controllers are
set as the main remote
controller.
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
receiver lamp
spcontroller dilay
Panasonic_PAC-i_IndoorUnit_US-le57 57
Panasonic_PAC-i_IndoorUnit_US-le57
57
2011/11/02 15:17:39
2011/11/02
15:17:39