Viking VBCV42381 Installation Instructions - Page 3

INSTALLING HOOD CANOPY Indoor/Outdoor VWH Models Only

Page 3 highlights

HEIGHT OF INDOOR HOOD The bottom of the hood should be 30" (76.2 cm) min. to 36" (91.4 cm) max. above the countertop. This would typically result in the bottom of the hood being 66" (167.6 cm) to 72" (182.9 cm) above the floor. The bottom of the hood should never be more than 72" (182.9 cm) above the floor or more than 36" (91.4 cm) above the countertop. These dimensions provide for safe and efficient operation of the hood. WALL INSTALLATION ISLAND INSTALLATION 18" (45.7 cm) 24" or 27" (61.0 cm or 68.6 cm) 30" (76.2 cm) Min. 36" (91.4 cm) Max. 66" - 72" (167.6 cm 182.9 cm) 36" (91.4 cm) Countertop 18" (45.7 cm) 30" (76.2 cm) Min. 36" (91.4 cm) Max. 30" (76.2 cm) 66" - 72" (167.6 cm 182.9 cm) 36" (91.4 cm) Countertop HEIGHT OF OUTDOOR HOOD The bottom of the hood should be 30" (76.2 cm) to 36" (91.4 cm) above the grill surface. The hood should be installed 41/2" (11.4 cm) plus the distance between the back trim and surface from the back wall. (NOTE: There is a 3" minimum clearance from the back trim to noncombustible surfaces and a 24" minimum to combustible surfaces.) This will require building the hood out from the wall. Any combustible material used for this purpose must be covered with locally supplied stainless steel. It is also recommended a backsplash be used with outdoor installations. 18" (45.7 cm) Canopy 27" (68.6 cm) 30" (76.2 cm) min. 36" (91.4 cm) max. DIM "X" plus 4-1/2" (11.4 cm) Soffit DIM "X" -Min. 3" (7.6 cm) to non-combustible surface -Min. 24" (61.0 cm) to combustible surface PREPARING FOR HOOD INSTALLATION Plan where the ductwork will be located. See pages 9-12 for rough-in dimensions. Install proper-sized duct work, and roof or wall cap for the type of blower you are using. Adjust your measurements for various heights of ceilings, soffits, cabinets, or ranges/rangetops. Exterior Blower Roof Cap 7" Round Duct Roof Cap 10" Round Duct 12" Duct Cover or Soffit 10" Round Duct 12" (30.5 cm) 12" Duct Cover or Soffit 12" (30.5 cm) 300 or 600 CFM Single Blower Interior-Power - Typical Ductwork 1200 CFM Single Blower Interior-Power - Typical Ductwork 900, 1200, or 1500 CFM Exterior-Power - Typical Ductwork ELECTRICAL SUPPLY Run 120 VAC electrical power cable from service panel to installation location. See "Basic Specifications" on page 3 for the maximum amp requirements. INSTALLING HOOD CANOPY (Indoor/Outdoor VWH Models Only) Center the wood strip (provided locally - see drawing for dimensions) and attach to wall. Using the slot located on the backside of the canopy, place the hood onto the wood strip. Secure the hood to strip with mounting screws provided. Make sure that the wood strip mounting screws are driven into the framing and not just the drywall. Use additional mounting screws (and wall anchors if necessary) in the other holes. 113/16" (4.6 cm) NOTE: BECAUSE OF THE WEIGHT OF THE HOOD - MAKE SURE THAT THE WOOD STRIP MOUNTING SCREWS ARE DRIVEN INTO THE FRAMING AND NOT JUST THE DRYWALL. IT MAY BE NECESSARY TO DRILL ADDITIONAL HOLES IN THE CANOPY FOR PROPER ALIGNMENT. Top Mounting Holes Wood Strip (provided locally- 11/2" x3/4") 11/2" (3.8 cm) 3/4"(1.9 cm) Slot for Wood Strip Rear Mounting Holes 4 5

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12

5
PREPARING FOR HOOD INSTALLATION
Plan where the ductwork will be located. See pages 9-12 for rough-in dimensions. Install proper-sized duct work, and
roof or wall cap for the type of blower you are using. Adjust your measurements for various heights of ceilings, soffits,
cabinets, or ranges/rangetops.
Roof Cap
7” Round
Duct
Roof Cap
10” Round
Duct
12” Duct Cover
or Soffit
300 or 600 CFM Single Blower
Interior-Power - Typical Ductwork
1200 CFM Single Blower
Interior-Power - Typical Ductwork
Exterior Blower
10” Round
Duct
12” Duct
Cover
or Soffit
12”
(30.5 cm)
900, 1200, or 1500 CFM
Exterior-Power - Typical Ductwork
12”
(30.5 cm)
ELECTRICAL SUPPLY
Run 120 VAC electrical power cable from service panel to installation location. See “Basic Specifications” on page 3
for the maximum amp requirements.
Top Mounting
Holes
Wood Strip
(provided locally- 1
1
/2”
x
3
/
4”
)
Slot for Wood Strip
Rear Mounting
Holes
1
1
/
2”
(3.8 cm)
3
/
4”
(1.9 cm)
1
13
/
16”
(4.6 cm)
INSTALLING HOOD CANOPY (Indoor/Outdoor VWH Models Only)
Center the wood strip (provided locally - see drawing for dimensions) and attach to wall. Using the slot located on the
backside of the canopy, place the hood onto the wood strip. Secure the hood to strip with mounting screws provided.
Make sure that the wood strip mounting screws are driven into the framing and not just the drywall. Use additional
mounting screws (and wall anchors if necessary) in the other holes.
NOTE: BECAUSE OF
THE WEIGHT OF THE
HOOD - MAKE SURE
THAT THE WOOD STRIP
MOUNTING SCREWS
ARE DRIVEN INTO THE
FRAMING AND NOT
JUST THE DRYWALL. IT
MAY BE NECESSARY TO
DRILL ADDITIONAL
HOLES IN THE CANOPY
FOR PROPER
ALIGNMENT.
HEIGHT OF INDOOR HOOD
The bottom of the hood should be 30” (76.2 cm) min. to 36” (91.4 cm) max. above the countertop. This would
typically result in the bottom of the hood being 66” (167.6 cm) to 72” (182.9 cm) above the floor. The bottom of the
hood should never be more than 72” (182.9 cm) above the floor or more than 36” (91.4 cm) above the countertop.
These dimensions provide for safe and efficient operation of the hood.
24” or 27”
(61.0 cm or 68.6 cm)
36”
(91.4 cm)
30”
(76.2 cm)
ISLAND INSTALLATION
WALL INSTALLATION
36”
(91.4 cm)
30” (76.2 cm) Min.
36” (91.4 cm) Max.
Countertop
30” (76.2 cm) Min.
36” (91.4 cm) Max.
18” (45.7 cm)
18” (45.7 cm)
66” - 72”
(167.6 cm -
182.9 cm)
66” - 72”
(167.6 cm -
182.9 cm)
HEIGHT OF OUTDOOR HOOD
The bottom of the hood should be 30”
(76.2 cm) to 36” (91.4 cm) above the grill
surface. The hood should be installed 4-
1/2” (11.4 cm) plus
the distance between
the back trim and surface from the back
wall. (NOTE: There is a 3” minimum
clearance from the back trim to non-
combustible surfaces and a 24” minimum
to combustible surfaces.) This will require
building the hood out from the wall. Any
combustible material used for this purpose
must be covered with locally supplied
stainless steel. It is also recommended a
backsplash be used with outdoor
installations.
18”
(45.7 cm)
Canopy
Soffit
DIM “X”
plus 4-1/2” (11.4 cm)
30” (76.2 cm) min.
36” (91.4 cm) max.
DIM “X”
-Min. 3” (7.6 cm) to
non-combustible surface
-Min. 24” (61.0 cm) to
combustible surface
27”
(68.6 cm)
Countertop
4