Whirlpool CEM2750KQ Installation Instructions - Page 4

Warning

Page 4 highlights

An exhaust hood should cap the exhaust vent to prevent exhausted air from returning into the dryer. The outlet of the hood must be at least 12 inches (30.5 cm) from the ground or anything else that may be in the path of the exhaust. Four-inch outlet hood is preferred. However, a 2-1/2-inch (6.4 cm) outlet exhaust hood may be used. A 2-1/2-inch (6.4 cm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary exhaust system is required. A main exhaust vent can be used for exhausting a group of dryers. Main exhaust vent should be sized to remove 200 CFM of air per dryer. Large-capacity lint screens of proper design may be used in the main exhaust vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room. dryer exhaust vent 30° max. dryer exhaust vent air flow main collector vent 30° max. dryer exhaust vent dryer exhaust vent 30° max. Back-draft Damper Kits, Part No. 3391910, are available from your Whirlpool dealer and should be installed in each dryer's exhaust vent to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main exhaust vent. Unobstructed air openings are required. Each exhaust vent should enter the main vent at an angle pointing in the direction of the airflow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents. The maximum angle of each vent entering the main vent should be no more than 30°. Keep air openings free of dry cleaning fluid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and loads being dried. A clean-out cover should be located on the main exhaust vent for periodically cleaning of the exhaust system. Page 4 An exhaust hood should cap the outside end of the main vent to prevent exhausted air from returning to the dryers. If an exhaust hood cannot be used, the outside end of the main vent should have a sweep elbow directed downward. If the main vent travels vertically through the roof, rather than through the wall, install 180° sweep elbow on the end of vent at least 2 feet (61 cm) above the highest part of the building. The opening wall or roof shall have a diameter 1/2 inch (1.3 cm) larger than the exhaust vent diameter. The exhaust vent should be centered in the opening. exhaust hood or sweep elbow wall horizontal vent main exhaust vent 2 ft. (61 cm) min. above highest point of building wall 180° sweep elbow main collector vent vertical vent roof Do Not install screening or cap over end of vent. Gas Dryer Gas requirements WARNING Explosion Hazard Use a new AGA or CSA approved gas supply line. Install a shut-off valve. Securely tighten all gas connections. If connected to LP, have a qualified person make sure gas pressure does not exceed 13" (33 cm) water column. Examples of a qualified person include licensed heating personnel, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire. OBSERVE ALL GOVERNING CODES AND ORDINANCES. A. This installation must conform with local codes, or in absence of local codes with the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the CAN/CGA - B149 installation codes. B. The design of this dryer has been certified by the CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at the B.T.U. rating indicated on the model/serial plate. Burner input adjustments are not required when the dryer is operated up to this elevation. When installed above 10,000 feet (3048 m), a four percent (4%) reduction of the burner B.T.U. rating shown on the model/serial plate is required for each 1,000 foot (305 m) increase in elevation. For assistance when converting to other gas types and/or installing above 10,000 feet (3048 m) elevation, contact your local service company.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

exhaust
hood or
sweep
elbow
180°
sweep
elbow
wall
wall
roof
main exhaust vent
horizontal vent
2 ft. (61 cm)
min. above
vertical vent
highest point of
building
main collector
vent
Do Not
install screening or cap over
end of vent.
Gas requirements
OBSERVE ALL GOVERNING CODES
AND ORDINANCES.
Page 4
An
exhaust hood
should cap the
outside end of the main vent to
prevent exhausted air from returning
to the dryers. If an exhaust hood
cannot be used, the outside end of
the main vent should have a sweep
elbow directed downward. If the
main vent travels vertically through
the roof, rather than through the wall,
install 180° sweep elbow on the end
of vent at least 2 feet (61 cm) above
the highest part of the building. The
opening wall or roof shall have a
diameter 1/2 inch (1.3 cm) larger than
the exhaust vent diameter. The
exhaust vent should be centered in
the opening.
A.
This installation must conform
with local codes, or in absence of
local codes with the National Fuel
Gas Code ANSI Z223.1/NFPA 54 or the
CAN/CGA - B149 installation codes.
B.
The design of this dryer has
been certified by the CSA
International for use at altitudes up to
10,000 feet (3048 m) above sea level
at the B.T.U. rating indicated on the
model/serial plate. Burner input
adjustments are not required when
the dryer is operated up to this
elevation.
When installed above 10,000 feet
(3048 m), a four percent (4%)
reduction of the burner B.T.U. rating
shown on the model/serial plate is
required for each 1,000 foot (305 m)
increase in elevation. For assistance
when converting to other gas types
and/or installing above 10,000 feet
(3048 m) elevation, contact your
local service company.
Four-inch outlet hood is preferred.
However, a 2-1/2-inch (6.4 cm) outlet
exhaust hood may be used. A
2-1/2-inch (6.4 cm) outlet creates
greater back pressure than other
hood types. For permanent
installation, a stationary exhaust
system is required.
A main exhaust vent
can be used for
exhausting a group of dryers. Main
exhaust vent should be sized to
remove 200 CFM of air per dryer.
Large-capacity lint screens of proper
design may be used in the main
exhaust vent if checked and cleaned
frequently. The room where the dryers
are located should have make-up air
equal to or greater than the CFM of
all the dryers in the room.
Back-draft Damper Kits,
Part No.
3391910, are available from your
Whirlpool dealer and should be
installed in each dryer's exhaust vent
to prevent exhausted air from
returning into the dryers and to keep
the exhaust in balance within the
main exhaust vent. Unobstructed air
openings are required.
Each exhaust vent
should enter the
main vent at an angle pointing in the
direction of the airflow. Vents entering
from the opposite side should be
staggered to reduce the exhausted
air from interfering with the other
vents.
The
maximum angle
of each vent
entering the main vent should be no
more than 30°.
Keep air openings free of dry
cleaning fluid fumes. Fumes create
acids which, when drawn through the
dryer heating units, can damage
dryers and loads being dried.
A
clean-out cover
should be located
on the main exhaust vent for
periodically cleaning of the exhaust
system.
dryer exhaust vent
dryer exhaust vent
main collector vent
air flow
30° max.
30° max.
dryer exhaust vent
dryer exhaust vent
30° max.
An
exhaust hood
should cap the
exhaust vent to prevent exhausted air
from returning into the dryer. The
outlet of the hood must be at least
12 inches (30.5 cm) from the ground
or anything else that may be in the
path of the exhaust.
WARNING
Explosion Hazard
Use a new AGA or CSA
approved gas supply line.
Install a shut-off valve.
Securely tighten all gas
connections.
If connected to LP, have a
qualified person make sure gas
pressure does not exceed 13"
(33 cm) water column. Examples
of a qualified person include
licensed heating personnel,
authorized gas company
personnel, and authorized
service personnel.
Failure to do so can result in
death, explosion, or fire.
Gas Dryer