Fluke 1503 FE 1503-1507 Users Manual - Page 20
Measuring Earth-Bond Resistance, until you release
View all Fluke 1503 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
1507/1503 Users Manual • The primary display shows ---- until you press the T button and a valid resistance reading is obtained. • The high voltage symbol (Y) along with a primary display of >2 V warns if voltage greater than 2 V ac or dc is present. In this condition, the test is inhibited. Disconnect the Tester and remove power before proceeding. • If the Tester chirps when you press the T button, the test is inhibited because voltage is present at the probes. 5. Push and hold the T button to start the test. The t icon appears on the lower portion of the display until you release the T button. The resistance reading appears on the primary display until a new test is started or a different function or range is selected. When resistance is higher than the maximum display range, the Tester displays the > symbol and the maximum resistance for the range. . 12 1507 INSULATION TESTER bbw04f.eps Figure 6. Measuring Earth-Bond Resistance