Specifications
Preparing your work area
Case size
17.5 × 7 × 28 inches (44.5 × 17.8 × 71.1 cm) (4U)
Weight
Minimum configuration: 57 lbs. (25.9 kg)
Maximum configuration: 88 lbs. (39.9 kg)
Required
clearances for
ventilation
Front: 3 inches (7.6 cm), inlet airflow <95°F (35°C)
Rear: 4.5 inches (11.4 cm), no airflow restriction
Side: 1 inch (2.5 cm)
Required
ventilation
152 to 160 CFM
Power
requirements
Voltage (110): 90 V
rms
minimum, 132 V
rms
maximum, 8 A
rms
Voltage (220): 180 V
rms
minimum, 264 V
rms
maximum, 4 A
rms
(Amperage is total system power, with two or three power supply
modules installed, with one or two AC power cords)
Frequency: 47 Hz minimum, 63 Hz maximum
Warning
The cabinet must be anchored to an unmovable support
to prevent the cabinet from falling over when one or more
servers are fully extended from the cabinet.
You are responsible for installing an AC power disconnect
for the cabinet. The main disconnect must be readily
accessible, and it must be labeled as controlling power to
the entire cabinet, not just to this server.
The cabinet must provide enough air flow to the front of
the system to maintain proper cooling. The operating
temperature of the server must not go below 50°F (10°C)
or rise above 95°F (35°C). Extreme fluctuations in
temperature may damage the server or cause it to operate
unreliably.