Haier AB122MCERA Operation Manual - Page 36
Haier AB122MCERA Manual
View all Haier AB122MCERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Electrical Wiring Status of SW08-[6] Controlling Method ON Wired control( include one control to multiple units, two controls to one unit and one control to one unit) OFF Remote control © Wired Controller Code Settings Serial No. Type Switch Status Choice of room o J03 temp. indications 1 Switchover of main SW01-[1] & auxiliary wired controllers ON I OFFI SW01-[2] Switchover of Centigrade & Fahrenheit ON IOFFI Schedule ON D1 compression function I OFFI D2 Compulsive defrosting ON IOFFI Switchover Function There is no indication for room temperature Automatic reset after power failure Set to auxiliary wired controller Set to main wired controller Indicating Fahrenheit Indicating Centigrade Indoor units perform schedule compression Normal control Sending "Compulsive Defrosting" signal to indoor units Normal control • D1 and D2 are diodes. Turn to "OFF" to disconnect holes of both sides while turn to "ON" to strap the holes of two sides with a guide line. • The code/ overline/ diode in the gray frame indicates that safety operation can be done by opening the shell of remote control. • Only when dual line controls control one indoor unit can one of the line control be set to auxiliary line control by setting SW01-[1] to "ON" while keeping the settings of others "OFF". Difference between Main Wired Controller and Auxiliary Wired Controller) Comparison Items Main wired controller Auxiliary wired controller Functions All functions It can only set shutdown, mode, air quantity, temperature and swinging. 34