[24 A (PDU current rating) / 6.4 A (server total input current rating)] = 3

Page 14 highlights

Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks 14 Compaq Confidential - Need to Know Required 2 [24 A (PDU current rating) / 6.4 A (server total input current rating)] = 3 These PDUs can support a maximum of 3 servers at full server input current ratings. For more information on high-voltage PDUs, refer to the "Power Distribution Unit High-Voltage Models for North America and International Use, (NA CPQ # 295363-002; INT'L CPQ # 295363-B31)" website: www.compaq.com/products/servers For more information on low-voltage PDUs, refer to the "Power Distribution Unit Low-Voltage Models for North America and International Use" website: www.compaq.com/products/servers Selecting Server Power Cords The appropriate server power cord to use depends on the cable management system installed in the rack. Generally, the sliding rail cable management system requires a power cord that is 1.8288 m (6 ft) in length. This length provides enough slack for the power cord to route through the cable management arm. High-Voltage Y-Cables The Vertical-Mount PDU Bracket with High-Voltage Cables kit includes 11 Y-cables, each of which is 3.0 m (10 ft) long. The single-cord PDU section is 1.8 m (6 ft) long, and the dual-cord server section is 1.3 m (4 ft) long. See Table 7 for part numbers. Y-cables have a single-cord section with an IEC connector that connects to the PDU, a dividing joint in the center, and a dual-cord section with IEC connectors that connect to the servers. One Y-cable supplies power from the PDU to two ProLiant DL380 Generation 2 servers in the standard configuration or one ProLiant DL380 Generation 2 server in the maximum configuration. CAUTION: When installing server power cords into the PDUs, ensure that the load is balanced among the output circuit breakers. Do not exceed the ratings of the circuit breakers. Table 7. Compaq High-Voltage Power Cables Description Vertical-Mount PDU Bracket with Highvoltage Cables kit 10A IEC-to-IEC Cables kit Compaq Part # Description 166097-B21 This kit includes two sets of PDU brackets and 11 Ycables. Each cable is 10-ft long with a 6-ft section on the single-side and 4-ft sections on the dual-side. 142257-001 (6 ft) 142257-002 (8 ft) 142257-003(10 ft) The IEC-to-IEC cables can be used either as individual power cords for the server or to extend the length of the high-voltage Y-cables. The cables are available in six-, eight-, and ten-foot lengths. The ProLiant DL380 Generation 2 Server ships with one 10-ft IEC to IEC cable, part number 142257-003. 14UH-0701A-WWEN

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

Compaq ProLiant DL380 Generation 2 Server High-Density Deployment in Compaq Racks
14
Compaq Confidential - Need to Know Required
14UH-0701A-WWEN
2 [24 A (PDU current rating) / 6.4 A (server total input current rating)] = 3
These PDUs can support a maximum of 3 servers at full server input current ratings.
For more information on high-voltage PDUs, refer to the “Power Distribution Unit High-Voltage
Models for North America and International Use, (NA CPQ # 295363-002; INT'L CPQ #
295363-B31)” website:
www.compaq.com/products/servers
For more information on low-voltage PDUs, refer to the “Power Distribution Unit Low-Voltage
Models for North America and International Use” website:
www.compaq.com/products/servers
Selecting Server Power Cords
The appropriate server power cord to use depends on the cable management system installed in
the rack. Generally, the sliding rail cable management system requires a power cord that is
1.8288 m (6 ft) in length. This length provides enough slack for the power cord to route through
the cable management arm.
High-Voltage Y-Cables
The Vertical-Mount PDU Bracket with High-Voltage Cables kit includes 11 Y-cables, each of
which is 3.0 m (10 ft) long. The single-cord PDU section is 1.8 m (6 ft) long, and the dual-cord
server section is 1.3 m (4 ft) long. See Table 7 for part numbers.
Y-cables have a single-cord section with an IEC connector that connects to the PDU, a dividing
joint in the center, and a dual-cord section with IEC connectors that connect to the servers. One
Y-cable supplies power from the PDU to two ProLiant DL380 Generation 2 servers in the
standard configuration or one ProLiant DL380 Generation 2 server in the maximum
configuration.
CAUTION:
When installing server power cords into the PDUs, ensure that the load is
balanced among the output circuit breakers. Do not exceed the ratings of the circuit
breakers.
Table 7.
Compaq High-Voltage Power Cables
Description
Compaq Part #
Description
Vertical-Mount PDU Bracket with High-
voltage Cables kit
166097-B21
This kit includes two sets of PDU brackets and 11 Y-
cables. Each cable is 10-ft long with a 6-ft section on
the single-side and 4-ft sections on the dual-side.
10A IEC-to-IEC Cables kit
142257-001 (6 ft)
142257-002 (8 ft)
142257-003(10 ft)
The IEC-to-IEC cables can be used either as individual
power cords for the server or to extend the length of the
high-voltage Y-cables. The cables are available in six-,
eight-, and ten-foot lengths. The ProLiant DL380
Generation 2 Server ships with one 10-ft IEC to IEC
cable, part number 142257-003.