Honeywell WAVE2EX Setup Guide - Page 36

Powerline Carrier Device, programming, Device number, Device action, Start event type, Start zone - siren manual

Page 36 highlights

LYNXR-I Installation and Setup Guide ✻80 Device Programming Menu Mode The following explains these prompts in detail. The left two columns identify the prompts and list the available entries. The right-most column provides a further explanation of the entries. Note: Entering a number other than one specified will give unpredictable results. 80 A 0I b aa C et d zl Powerline Carrier Device programming 0 = exit mode 1 = enter mode Device number 01-08 = device number to be programmed [✻] = continue 00 = exit Device Programming mode Device action 0 = No response 1 = Close for 2 seconds 2 = Close and Stay Closed 3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF) [✻] = continue [#] = return to previous prompt Start event type 0 = Not used 3 = Trouble 1 = Alarm [✻] = continue 2 = Fault [#] = return to previous prompt Start zone list 1-3 = zone list number (to be programmed in field ✻81) 0 = zone list not used for this device [✻] = continue [#] = return to previous prompt Entering "1" advances to the next prompt below. Entering "0" exits mode, upon which this prompt blinks, indicating the mode is inactive. Enter device numbers as 2-digit entries. Enter the 1-digit action (0-3) for the device being programmed (current action is displayed). NOTES: 1. If "3" is entered (pulse), only up to 3 different devices can be pulsed if one of the devices is a siren/horn (X10 Powerhouse Security model SH10A). In addition, the siren/horn cannot be manually activated using the lights on/lights off keypad commands. 2. If using an X10 Powerhouse Security SH10A siren: • you must use device action "3." • you must change the device action default to "3" if using default table 2 or 4 Enter the 1-digit event type (0-3) to activate the device being programmed. A zone list must be used in conjunction with an event. If a zone type/system operation is to be used instead of an event, enter "0". If a zone list will be used to start the device action, enter the zone list number at this prompt. E zt F zl Start zone type 01-58 = zone type to start this device action (select only those that are applicable) 00 = zone type not used for this device [✻] = continue [#] = return to previous prompt Stop zone list 1-3 = zone list to stop this device action 0 = zone list not used [✻] = continue [#] = return to previous prompt If a zone type or system operation will be used to start the device action, enter the appropriate 2-digit code for the device being programmed (see table that follows). Choices for zone types 00 = Not Used 01 = Entry/Exit #1 02 = Entry/Exit #2 03 = Perimeter 04 = Interior Follower 05 = Trouble Day/Alarm Night 06 = 24 Hr Silent 07 = 24 Hr Audible 08 = 24 Hr Aux 09 = Fire 10 = Interior w/Delay 24 = Silent Burglary Choices for system operation 20 = Arming-Stay 33 = Any Alarm (except 42 = Sys. Batt. Low zt 08 & 09) 21 = Arming-Away 36 = At Bell Timeout** 43 = Comm. Failure 22 = Disarm. (Code 38 = Chime 52 = Kissoff + OFF) 31 = End of Exit 39 = Any Fire Alarm 58 = Duress Time 32 = Start of Entry 40 = Bypassing Time ** Or at Disarming (which ever occurs earlier) If a zone list will be used to STOP, or restore, the device action, enter the zone list number 1, 2, or 3 (to be programmed in ✻81 mode). If not used, enter "0". IA zt Stop zone type 01-58 = zone type to start this device action (select only those that are applicable) 00 = zone type not used for this device [✻] = continue [#] = return to previous prompt If a zone type or system operation will be used to STOP the device action, enter the appropriate 2-digit code (see the "ZT" choices listed above). If not, enter 00. The display then returns to the DEVICE NUMBER prompt (A) so that you can enter the next device number to be programmed, or enter [0][0] to end device programming. - 36 -

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72

LYNXR-I Installation and Setup Guide
- 36 -
80 Device Programming Menu Mode
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Note:
Entering a number other than one specified will give unpredictable results.
80
Powerline Carrier Device
programming
0 = exit mode
1 = enter mode
Entering “1” advances to the next prompt below.
Entering “0” exits mode, upon which this prompt blinks, indicating
the mode is inactive.
A
0I
Device number
01-08 =
device number to be programmed
[
] = continue
00 = exit Device Programming mode
Enter device numbers as 2-digit entries.
b
aa
Device action
0 = No response
1 = Close for 2 seconds
2 = Close and Stay Closed
3 = Continuous Pulse on & off
(1 sec ON, 1 sec
OFF)
[
] = continue
[#] = return to previous prompt
Enter the 1-digit action (0-3) for the device being programmed
(current action is displayed).
NOTES:
1. If
“3” is entered (pulse), only up to 3 different devices can be
pulsed if one of the devices is a siren/horn (X10 Powerhouse
Security model SH10A). In addition, the siren/horn cannot be
manually activated using the lights on/lights off keypad
commands.
2.
If using an X10 Powerhouse Security SH10A siren:
you must use device action “3.”
you must change the device action default to “3” if using default
table 2 or 4
C
et
Start event type
0 = Not used
3 = Trouble
1 = Alarm
[
] = continue
2 = Fault
[#] = return to previous
prompt
Enter the 1-digit event type (0-3) to activate the device being
programmed. A zone list must be used in conjunction with an event. If
a zone type/system operation is to be used instead of an event, enter
“0”.
d
zl
Start zone list
1-3 = zone list number (to be programmed in
field
81)
0 = zone list not used for this device
[
] = continue
[#] = return to previous prompt
If a zone list will be used to start the device action, enter the zone list
number at this prompt.
E
zt
Start zone type
01-58 = zone type to start this device action
(select only those that are applicable)
00 = zone type not used for this device
[
] = continue
[#] = return to previous prompt
If a zone type or system operation will be used to start the device
action, enter the appropriate 2-digit code for the device being
programmed (see table that follows).
Choices for zone types
00 = Not Used
04 = Interior Follower
08 = 24 Hr Aux
01 = Entry/Exit #1
05 = Trouble Day/Alarm Night
09 = Fire
02 = Entry/Exit #2
06 = 24 Hr Silent
10 = Interior w/Delay
03 = Perimeter
07 = 24 Hr Audible
24 = Silent Burglary
Choices for system operation
20 = Arming–Stay
33 =
Any Alarm (except
zt 08 & 09)
42 =
Sys. Batt. Low
21 = Arming–Away
36 = At Bell Timeout**
43 = Comm. Failure
22 =
Disarm. (Code
+ OFF)
38 = Chime
52 =
Kissoff
31 =
End of Exit
Time
39 = Any Fire Alarm
58 =
Duress
32 = Start of Entry
Time
40 =
Bypassing
** Or at Disarming (which ever occurs earlier)
F
zl
Stop zone list
1-3 = zone list to stop this device action
0 = zone list not used
[
] = continue
[#] = return to previous prompt
If a zone list will be used to STOP, or restore, the device action, enter
the zone list number 1, 2, or 3 (to be programmed in
81 mode). If not
used, enter “0”.
IA
zt
Stop zone type
01-58 = zone type to start this device action
(select only those that are applicable)
00 = zone type not used for this device
[
] = continue
[#] = return to previous prompt
If a zone type or system operation will be used to STOP the device
action, enter the appropriate 2-digit code (see the "ZT" choices listed
above). If not, enter 00.
The display then returns to the DEVICE NUMBER prompt (A) so
that you can enter the next device number to be programmed, or enter
[0][0] to end device programming.