Kenmore 3314 Owners Manual - Page 14

FitT&Pvalve, insulation, valve., Makesure, thathe, doesnotinterfere, withthelever, oftheT&

Page 14 highlights

FitT&Pvalveinsulationvevr alveM. akesurethatheinsulation doesnotinterferweiththeleveor ftheT&Pvalve. Secureal!insulatiounsingtape. HOT WATER OUTLET Temperature-Pressure Relief Valve DRAFT HOOD REUEF VALVE (OPTIONAL TOP T & P RELIEF VALVE NOT SHOWN) Explosion Hazard /---\ o Temperature@ressure relief valve must comply wffh ANSI Z2122 and ASME code • Properly sized temperaturepressure relief valve must be installed in opening provided, -Can result in overheating and ezcessive tank pressure o Can cause serious injury' or death, _--'(DO DISNCARGEPUPE NOT CAP OR PLUG) _DRA_N VALVE j FLOOR DRAON This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer. FIGURE1& The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 and the code requirements of ASME. If replaced, the codes, but not pressure relief paragraph. valve must meet the requirements of local less than a combination temperature and valve certified as indicated in the above The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged. The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 ram) above, or at any distance below the structural floor, see Figure 16. Be certain that no contact is made with any live electrica! part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. Water Damage Hazard Temperature-pressure relief valve discharge pipe must terminate at adequate drain. The Discharge Pipe: * Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. * Shall not be plugged or blocked. . Shall be of material listed for hot water distribution. . Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe. * Shall terminate at an adequate drain. * Shall not have any valve between the relief valve and tank. Water temperature over 125°F (52°0) can cause severe burns instantly resulting in severe injury or death Children, the elderly, and the physically or mentally disabled are at highest riskfor scald injury. Feel water before bathing or showering. Temperature limiting valves are available. Read instruction manual for safe temperature setting 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

FitT&Pvalve
insulation
over
valve.
Makesure
thathe
insulation
doesnotinterfere
withthelever
oftheT&Pvalve.
Secureal!insulation
using
tape.
Temperature-Pressure
Relief
Valve
/---\
Explosion
Hazard
o Temperature@ressure
relief valve
must
comply
wffh
ANSI
Z2122
and ASME
code
Properly
sized
temperature-
pressure
relief
valve
must
be
installed in opening
provided,
-Can
result
in
overheating
and
ezcessive
tank pressure
o Can cause serious injury' or death,
This
heater
is provided
with
a
properly
certified
combination
temperature
- pressure
relief
valve
by the
manufacturer.
The
valve
is
certified
by
a
nationally
recognized
testing
laboratory
that
maintains
periodic
inspection
of
production
of
listed
equipment
as meeting
the
requirements
for
Relief
Valves
and
Automatic
Gas
Shutoff
Devices
for
Hot
Water
Supply
Systems,
ANSI
Z21.22
and
the
code
requirements
of ASME.
If
replaced,
the
valve
must
meet
the
requirements
of
local
codes,
but
not
less
than
a
combination
temperature
and
pressure
relief
valve
certified
as
indicated
in
the
above
paragraph.
The
valve
must
be
marked
with
a maximum
set
pressure
not to
exceed
the
marked
hydrostatic
working
pressure
of the
water
heater
(150
psi
= 1,035
kPa)
and
a discharge
capacity
not
less
than
the
water
heater
input
rate
as shown
on
the
model
rating
plate.
For
safe
operation
of the
water
heater,
the
relief
valve
must
not
be
removed
from
its designated
opening
nor
plugged.
The temperature-pressure
relief
valve
must
be
installed
directly
into
the
fitting
of the
water
heater
designed
for the
relief
valve.
Position
the
valve
downward
and
provide
tubing
so
that
any
discharge
will
exit
only
within
6 inches
(153
ram)
above,
or
at
any distance
below
the
structural
floor,
see
Figure
16.
Be certain
that
no
contact
is
made
with
any
live
electrica!
part.
The
discharge
opening
must
not
be
blocked
or
reduced
in
size
under
any
circumstances.
Excessive
length,
over
30
feet
(9.14
m), or use
of more
than
four
elbows
can
cause
restriction
and
reduce
the
discharge
capacity
of the
valve.
No
valve
or other
obstruction
is to be placed
between
the
relief
valve
and
the
tank.
Do
not
connect
tubing
directly
to discharge
drain
unless
a
6
inch
air
gap
is provided.
To
prevent
bodily
injury,
hazard
to
life,
or property
damage,
the
relief
valve
must
be
allowed
to
discharge
water
in
quantities
should
circumstances
demand.
If the discharge
pipe
is not
connected
to
a drain
or
other
suitable
means,
the
water
flow
may
cause
property
damage.
HOT WATER
OUTLET
DRAFT
HOOD
REUEF
VALVE
(OPTIONAL
TOP
T&
P RELIEF
VALVE
NOT SHOWN)
DISNCARGEPUPE
_--'(DO
NOT CAP
OR
PLUG)
_DRA_N
VALVE
j
FLOOR
DRAON
FIGURE1&
Water
Damage
Hazard
Temperature-pressure
relief
valve
discharge
pipe
must
terminate
at adequate
drain.
The
Discharge
Pipe:
*
Shall
not
be
smaller
in size
than
the
outlet
pipe
size
of
the
valve,
or have
any
reducing
couplings
or other
restrictions.
*
Shall
not
be
plugged
or blocked.
.
Shall
be
of
material
listed
for
hot
water
distribution.
.
Shall
be
installed
so
as to
allow
complete
drainage
of
both
the
temperature-pressure
relief
valve,
and
the
discharge
pipe.
*
Shall
terminate
at an
adequate
drain.
*
Shall
not
have
any
valve
between
the
relief
valve
and
tank.
Water
temperature
over
125°F
(52°0)
can
cause
severe
burns
instantly resulting
in severe injury
or death
Children,
the
elderly,
and
the
physically
or
mentally
disabled
are at highest riskfor scald
injury.
Feel
water
before
bathing
or
showering.
Temperature
limiting
valves
are
available.
Read
instruction
manual for safe
temperature
setting
14