Kenmore 3314 Owners Manual - Page 23

Start, Up Conditions - dryer parts

Page 23 highlights

Start Up Conditions Thermal Expansion NOTE: Expansion tanks are pre-charged with a 40 psi air charge. [f the intact water pressure is higher than 40 psi, the expansion tank's air pressure must be adjusted to match that pressure, but must not be higher than 80 psi. Property Damage Hazard o Avoid water heater damage. o Install thermal expansion tank or device if necessary , Contact qualified installer or service agency. WATER HEATER (3) Water supply system may, because of such events as high line pressure, frequent cut-offs, and the effects of water hammer have installed devices such as pressure reducing valves, check valves, back flow preventers, etc., to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water. The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of water heater's temperature-pressure relief valve is reached, the valve will relief the excess pressure. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion, This is an unacceptable condition and must be corrected. It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank or device to relieve the pressure built by thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations. See Figure 26. (VERTICAL MOUNTING) WATER COLD INLET HEATER WATER FITTING FLOOR, CEILING JOBST, ETC, HOT COLD (1) EXPANSION (3) PRESSURE REDUCING VALVE WITH BY-PASS / TANK :_ t INLET COLD WATER SHUT-OFF ALTERNATE RECOMMENDED INSTALLATION (HORIZONTAL MOUNTING) Thermal Expansion Tank Specifications Mode_ Number 153.331020 153.331050 Tank Capacity In Gallons 2 5 Dimensions in Inches Diameter Lenqth 8 (203 ram) 12-3/4 (323 ram) 11 (279 ram) 14-3/4 (375 ram) Pipe Fitting On Tank 3/4" Mate 3/4" Mate Expansion Tank Sizing Chart F_GURE2& Strange Sounds Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions. Inlet* Water Pressure Water Heater Capacity (Gallons) 30 40 50 66 80 Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See Condensation section. Expansion Tank 40psi 50psi 2 2 2 55 2 2 2 55 Draft Hood Operation Capacity Needed 60psi 70psi 80psi 2 2 5 55 2 2 5 55 2 5 5 55 *Highest recorded inlet water pressure in a 24 hour period or Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the regulated water pressure, draft hood of the water heater with its burner firing. If the flame 23

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

Start
Up Conditions
Thermal
Expansion
Property
Damage
Hazard
o
Avoid
water
heater
damage.
o Install
thermal
expansion
tank
or device
if necessary
, Contact
qualified
installer
or service
agency.
NOTE:
Expansion
tanks
are
pre-charged
with
a 40
psi
air
charge.
[f the
intact water
pressure
is higher
than
40 psi,
the
expansion
tank's
air
pressure
must
be
adjusted
to
match
that
pressure,
but
must
not
be
higher
than
80 psi.
Water
supply
system
may,
because
of such
events
as high
line
pressure,
frequent
cut-offs,
and
the
effects
of
water
hammer
have
installed
devices
such
as pressure
reducing
valves,
check
valves,
back
flow
preventers,
etc.,
to
control
these
types
of
problems.
When
these
devices
are
not
equipped
with
an
internal
by-pass,
and
no other
measures
are taken,
the
devices
cause
the
water
system
to
be
closed.
As
water
is heated,
it
expands
(thermal
expansion)
and
closed
systems
do
not
allow
for the
expansion
of heated
water.
The
water
within
the
water
heater
tank
expands
as
it is heated
and
increases
the
pressure
of the
water
system.
If the
relieving
point
of
water
heater's
temperature-pressure
relief
valve
is
reached,
the
valve
will
relief
the
excess
pressure.
The
temperature-pressure
relief
valve
is
not
intended
for
the
constant
relief
of
thermal
expansion,
This
is an unacceptable
condition
and
must
be
corrected.
It is recommended
that
any devices
installed
which
could
create
a
closed
system
have
a
by-pass
and/or
the
system
have
an
expansion
tank
or device
to relieve
the pressure
built
by thermal
expansion.
Thermal
expansion
tanks
are available
from
Sears
stores
and
through
the
Sears
Service
Centers.
Contact
the
local
plumbing
inspector,
water
supplier
and/or
the
Sears
Service
Center
for
assistance
in
controlling
these
situations.
See
Figure
26.
Thermal
Expansion
Tank Specifications
Tank
Dimensions
Mode_
Capacity
in Inches
Number
In
Gallons
Diameter
Lenqth
153.331020
2
8 (203 ram)
12-3/4
(323 ram)
153.331050
5
11 (279 ram)
14-3/4 (375 ram)
Pipe
Fitting
On
Tank
3/4" Mate
3/4" Mate
Expansion
Tank Sizing
Chart
Water
Heater
Capacity
(Gallons)
Inlet*
Water
Pressure
40psi
50psi
60psi
70psi
80psi
30
40
50
66
80
Expansion
2
2
2
5
5
Tank
2
2
2
5
5
Capacity
2
2
5
5
5
Needed
2
2
5
5
5
2
5
5
5
5
*Highest
recorded
inlet water pressure
in a 24 hour period or
regulated
water
pressure,
WATER
HEATER
(3)
(VERTICAL
MOUNTING)
WATER
HEATER
COLD
WATER
INLET
FITTING
HOT
COLD
FLOOR,
CEILING
JOBST,
ETC,
(3)
PRESSURE
REDUCING
VALVE WITH
(1)
BY-PASS
EXPANSION
/
TANK
:_
t
INLET
COLD
WATERSHUT-OFF
ALTERNATE
RECOMMENDED
INSTALLATION
(HORIZONTAL
MOUNTING)
23
F_GURE2&
Strange
Sounds
Possible
noises
due
to
expansion
and
contraction
of
some
metal
parts
during
periods
of
heat-up
and
cool-down
do
not
represent
harmful
or
dangerous
conditions.
Condensation
causes
sizzling
and
popping
within
the
burner
area
during
heating
and
cooling
periods
and
should
be
considered
normal.
See
Condensation
section.
Draft
Hood
Operation
Check
draft
hood
operation
by
performing
a
worst
case
depressurization
of
the
building.
With
all doors
and
windows
closed,
and
with
all air
handling
equipment
and
exhaust
fans
operating
such
as furnaces,
clothes
dryers,
range
hoods
and
bathroom
fans,
a
match
flame
should
still
be
drawn
into
the
draft
hood
of the
water
heater
with
its burner
firing.
If the
flame