LG LAN121CNM Service Manual - Page 29
Air Purging, Air purging With Vacuum Pump
View all LG LAN121CNM manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 29 highlights
Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. • Pressure in the system rises. • Operating current rises. • Cooling(or heating) efficiency drops. • Moisture in the refrigerant circuit may freeze and block capillary tubing. • Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system. Air purging With Vacuum Pump Preparation • Do a leak test of all joints of the tubing(both • Check that each tubing(both liquid and gas side indoor and outdoor) and both gas and liquid side tubes) between the indoor and outdoor units have service valves. been properly connected and all wiring for the test Bubbles indicate a leak. Be sure to wipe off the run has been completed. Remove the service soap with a clean cloth. valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage. • After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder. Leak test • Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses. Indoor unit Manifold valve Pressure gauge Lo Hi Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close. • Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap. Outdoor unit Charge hose Nitrogen gas cylinder(in vertical standing position) To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. Service Manual 29