LG LAN121CNM Service Manual - Page 46
Evacuation
View all LG LAN121CNM manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 46 highlights
Troubleshooting Guide Evacuation (All amount of refrigerant leaked) Indoor unit Liquid side 3-Way valve Open Outdoor unit Gas side 3-Way valve Open Vacuum pump OPEN Lo CLOSE • Procedure (1) Connect the vacuum pump to the center hose of charge set center hose (2) Evacuation for approximately one hour. - Confirm that the gauge needle has moved toward -76 cmHg (vacuum of 4 mmHg or less). (3) Close the valve (Lo side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approxima-tely 5 minutes after turning off the vacuum pump). (4) Disconnect the charge hose from the vacuum pump. - Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted, replenish as needed. Use vacuum pump equipped with check value applied to be prevented from flowing backward. 46 Room Air Conditioner