RD GATE 2 SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR OFF / RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS ORCE GATE 2 ON OFF AUTO OPEN LOW BATT MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR INSTALLATION » LARGE METAL CONTROL BOX (XLM) MOUNT THE CONTROL BOX (XLM) The control box MUST be mounted within 5 feet (1.52 m) of the gate operator. 1 90° Mount the control box as high as possible for best radio reception. LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR 1 Open the control box. The control box door may be removed by opening the door 90°. Lift the door from the hinges and set aside until the installation is complete. 2 The control box can be mounted to a post with 'U' bolts. See chart below. The knock out will accommodate a 3/8" diameter 'U' bolt. 2 Type and Size Standard 3" Round Pipe Standard 4" Square Post Standard 6" Square Post 'U' Bolt Opening 3-1/2" 4" 6" 3 Select center mounting holes (top and bottom) knock out using a screwdriver and hammer. Use knock outs located at the 4 corners of the control box for wall or column mounting. 3 ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR LOOP INPUTS ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON OFF MAX RESET STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 ALARM CLOSE EDGE CLOSE EDGE LEARN XMITTER SET OPEN LIMIT ON OFF LOCK / BIPA RT DELAY GATE 1 SET CLOSE LIMIT LEARN LIMITS LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD OPEN EDGE/ PHOTO OPEN PHOTO CLOSE PHOTO FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX ACCESSORY SINGLE BPUOTWTEORN TIMER TO CLOSE OFF MAX 12 V OPEN BR SINGLE BUTTON GR RESET WH SYTLOP CTRL PWR BL CTRL PWR RD GATE 2 SHADOW CONTROL INPUTS LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR LEARN XMITTER ON OFF LOCK / BIPA RT DELAY OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY SET OPEN LIMIT GATE 1 SET CLOSE LIMIT LEARN LIMITS GATE 2 FORCE ON OFF AUTO OPEN LOW BATT OFF MAX ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON RESET OFF MAX STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY SET OPEN LIMIT G SET CLOSE LIMIT L L G FORCE A OFF MAX EARTH GROUND ROD INSTALLATION (REQUIRED) It is important to install the ground rod when using a metal control box to prevent serious injury to persons or damage to the operator. 1 Install earth ground rod within 3 feet (0.9 m) of the operator. 2 Connect ground rod with #12 copper wire to one of the two green ground screws inside the control box. The XLM control box wires the same as the standard control box. Follow all instructions for the standard control box. The illustrations show the standard control box, not the XLM control box. ALARM CLOSE EDGE SOL GND OPEN EDGE/ PHOTO MAGR LOCK ON OFF LEARN XMITTER LOCK / BIPA RT DELAY OPEN PHOTO GATE 1 NOTE: BR GR WH YL BL RD TheGATE1 additional CLOSE PHOTO standoffs are specifically designed to mount up to 3 Chamberlain loop detectors model LO7LP (not provided). ACCESSORY POWER 12 V BR SET OPEN LIMIT SET CLOSE LIMIT LEARN LIMITS GATE 2 FORCE ON OFF AUTO OPEN LOW BATT SINGLE BUTTON TIMER TO CLOSE OPEN SINGLE BUTTON CONTROL INPUTS GR RESET WH YL OFF MAX OFF MAX STOP CTRL PWR BL CTRL PWR RD GATE 2 LOOP INPUTS SHADOW INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR 19 Ground Screw Standoffs ALARM LOCK SOL GND MAGR GATE 1 BR GR WH YL BL RD ACCESSORY POWER 12 V BR GR WH YL BL RD GATE 2 LEARN XMITTER ON OFF LOCK / BIPA RT DELAY CLOSE EDGE OPEN EDGE/ PHOTO OPEN PHOTO SET OPEN LIMIT GATE 1 CLOSE PHOTO SET CLOSE LIMIT LEARN LIMITS FORCE GATE 2 ON OFF AUTO OPEN LOW BATT OFF MAX SINGLE BUTTON TIMER TO CLOSE OPEN CONTROL INPUTS SINGLE BUTTON OFF MAX RESET STOP CTRL PWR CTRL PWR SHADOW LOOP INPUTS INTERRUPT CHGR OVLD CTRL PWR AC PWR /SOLAR

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

19
INSTALLATION
» LARGE METAL CONTROL BOX (XLM)
MOUNT THE CONTROL BOX (XLM)
The control box MUST be mounted within 5 feet (1.52 m) of the gate operator.
Mount the control box as high as possible for best radio reception.
Open the control box. The control box door may be removed by opening the
door 90°. Lift the door from the hinges and set aside until the installation is
complete.
The control box can be mounted to a post with 'U' bolts. See chart below. The
knock out will accommodate a 3/8" diameter 'U' bolt.
90°
1
2
3
1
3
EARTH GROUND ROD INSTALLATION (REQUIRED)
It is important to install the ground rod when using a metal control box to prevent
serious injury to persons or damage to the operator.
Install earth ground rod within 3 feet (0.9 m) of the operator.
Connect ground rod with #12 copper wire to one of the two green ground
screws inside the control box.
The XLM control box wires the same as the standard
control box. Follow all instructions for the standard
control box. The illustrations show the standard control
box, not the XLM control box.
NOTE:
The additional standoffs are specifically designed to mount up to
3 Chamberlain loop detectors model LO7LP (not provided).
Ground Screw
Standoffs
1
2
2
Select center mounting holes (top and bottom) knock out using a screwdriver
and hammer. Use knock outs located at the 4 corners of the control box for
wall or column mounting.
Type and Size
'U' Bolt Opening
Standard 3" Round Pipe
3-1/2"
Standard 4" Square Post
4"
Standard 6" Square Post
6"