Maytag MEDB835DC W10240504 - Page 19

Temperature Levels Incorrect, Timed Dry, IMPORTANT, TIMED DRY

Page 19 highlights

FOR SERVICE TECHNICIAN'S USE ONLY NOTE: All thermistor resistance measurements must be made while dryer is unplugged and connector removed from ACU. OUTLET THERMISTOR RESISTANCE TEMP. °F (°C) 50° (10°) 60° (16°) 70° (21°) RES. RANGE k ohms 19.0-22.0 14.8-16.8 11.5-13.5 TEMP. °F (°C) 80° (27°) 90° (32°) 100° (38°) RES. RANGE k ohms 8.5-10.5 6.8-8.8 5.0-7.0  If the resistance is OK, the outlet thermistor is good. Proceed to step 4.  If the thermistor resistance does not agree with the table, replace the outlet thermistor. 4. Check P14-3 and P14-6 to dryer cabinet ground. If either pin indicates continuity to ground (short), replace wiring harness; otherwise, proceed to step 5. 5. If the preceding steps did not correct the problem, replace the ACU. Temperature Levels Incorrect - If no error code is displayed and the connections to the thermistor are good, check the exhaust temperature value at any or all of the temperature levels in question, using the Timed Dry cycle. IMPORTANT: Be sure EcoBoost or Energy Saver (if available) is turned OFF before testing. 1. Remove load from dryer and disconnect external vent. 2. Plug in dryer or reconnect power. 3. Run a TIMED DRY cycle (Mixed + Timed Dry on Whirlpool models) of at least 2 minutes in duration and select a temperature setting using heat. 4. Using a calibrated temperature probe, take a temperature measurement in the center of the exhaust outlet. The correct exhaust temperatures are as follows: EXHAUST TEMPERATURES TEMPERATURE SETTING (appearance may vary) HEAT TURNS OFF* °F (°C) HEAT TURNS ON °F (°C) 155° ± 5° (68° ± 3°) 140° ± 5° (60° ± 3°) 125° ± 5° (52° ± 3°) 105° ± 5° (41° ± 3°) 10-15° (6-8°) below the heat turn off temperature  If the temperature is not reached within ~7 minutes, check voltage level and vent blockage, and then retest.  If the temperature probe does not agree with temperature setting, replace the outlet thermistor.  If the temperature probe confirms the temperature setting, retest at a different temperature setting. 5. If the preceding steps did not correct the problem, replace the ACU. Inlet Thermistor NOTE: On the electric dryer, the inlet thermistor is part of the high thermostat assembly (see figure 10a). On the gas dryer, the inlet thermistor is located at the drum inlet duct (see figure 16, page 27). The ACU monitors the inlet temperature using the inlet thermistor. The inlet thermistor (along with the outlet thermistor) is used to detect air flow, and assists in calculating load size. 1. Unplug dryer or disconnect power. 2. Remove console to access the machine electronics. 3. Remove connector P14 from the ACU and measure the resistance between P14-1 and P14-2 at the connector. The following tables (electric & gas) give temperatures and their associated resistance values. NOTE: All thermistor resistance measurements must be made while dryer is unplugged and connector removed from ACU.  If the resistance is OK, the inlet thermistor is good. Proceed to step 4.  If the thermistor resistance does not agree with the table, replace the inlet thermistor. ELECT - INLET THERMISTOR RESISTANCE TEMP. °F (°C) 68° (20°) 77° (25°) 86° (30°) 95° (35°) 104° (40°) 113° (45°) 122° (50°) RES. RANGE k ohms 61.2-63.7 49.0-51.0 39.5-41.1 32.0-33.3 26.1-27.2 21.4-22.3 17.6-18.5 TEMP. °F (°C) 131° (55°) 140° (60°) 149° (65°) 158° (70°) 167° (75°) 176° (80°) RES. RANGE k ohms 14.5-15.3 12.1-12.8 10.2-10.7 8.5-9.0 7.2-7.6 6.1-6.5 GAS - INLET THERMISTOR RESISTANCE TEMP. °F (°C) 68° (20°) 77° (25°) 86° (30°) 95° (35°) 104° (40°) 113° (45°) 122° (50°) RES. RANGE k ohms 57.5-67.6 46.1-53.8 37.4-43.1 30.4-34.7 24.9-28.2 20.5-23.0 16.9-18.9 TEMP. °F (°C) 131° (55°) 140° (60°) 149° (65°) 158° (70°) 167° (75°) 176° (80°) RES. RANGE k ohms 14.1-15.6 11.8-12.9 9.9-10.8 8.4-9.0 7.1-7.6 6.0-6.4 DO NOT REMOVE OR DESTROY PAGE 19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

PAGE 19
FOR SERVICE TECHNICIAN’S USE ONLY
DO NOT REMOVE OR DES
TROY
NOTE:
All thermistor resistance measurements
must be made while dryer is unplugged and
connector removed from ACU.
If the resistance is OK, the outlet thermistor
is good. Proceed to step 4.
If the thermistor resistance does not agree
with the table, replace the outlet thermistor.
4.
Check P14-3 and P14-6 to dryer cabinet
ground. If either pin indicates continuity
to ground (short), replace wiring harness;
otherwise, proceed to step 5.
5.
If the preceding steps did not correct the
problem, replace the ACU.
Temperature Levels Incorrect –
If no error code
is displayed and the connections to the thermistor
are good, check the exhaust temperature value
at any or all of the temperature levels in question,
using the
Timed Dry
cycle.
IMPORTANT:
Be sure EcoBoost or Energy Saver
(if available) is turned OFF before testing.
1.
Remove load from dryer and disconnect
external vent.
2.
Plug in dryer or reconnect power.
3.
Run a
TIMED DRY
cycle (Mixed + Timed
Dry on Whirlpool models) of at least 2 minutes
in duration and select a temperature setting
using heat.
4.
Using a calibrated temperature probe,
take a temperature measurement in the center
of the exhaust outlet. The correct exhaust
temperatures are as follows:
If the temperature is not reached within
~7 minutes, check voltage level and vent
blockage, and then retest.
If the temperature probe does not agree
with temperature setting, replace the outlet
thermistor.
TEMP.
°F (°C)
RES.
RANGE
k ohms
TEMP.
°F (°C)
RES.
RANGE
k ohms
50° (10°)
19.0–22.0
80° (27°)
8.5–10.5
60° (16°)
14.8–16.8
90° (32°)
6.8–8.8
70° (21°)
11.5–13.5
100° (38°)
5.0–7.0
OUTLET THERMISTOR RESISTANCE
TEMPERATURE
SETTING
HEAT TURNS OFF*
°F (°C)
HEAT TURNS ON
°F (°C)
155° ± 5°
(68° ± 3°)
140° ± 5°
(60° ± 3°)
125° ± 5°
(52° ± 3°)
105° ± 5°
(41° ± 3°)
EXHAUST TEMPERATURES
10–15° (6–8°)
below the
heat turn off
temperature
(appearance may vary)
If the temperature probe confirms the
temperature setting, retest at a different
temperature setting.
5.
If the preceding steps did not correct the
problem, replace the ACU.
Inlet Thermistor
NOTE:
On the electric dryer, the inlet thermistor
is part of the high thermostat assembly
(see figure 10a). On the gas dryer, the inlet
thermistor is located at the drum inlet duct
(see figure 16, page 27).
The ACU monitors the inlet temperature using
the inlet thermistor. The inlet thermistor (along
with the outlet thermistor) is used to detect air
flow, and assists in calculating load size.
1.
Unplug dryer or disconnect power.
2.
Remove console to access the machine
electronics.
3.
Remove connector
P14
from the ACU and
measure the resistance between P14-1 and
P14-2 at the connector. The following tables
(electric & gas) give temperatures and their
associated resistance values.
NOTE:
All thermistor resistance measurements
must be made while dryer is unplugged and
connector removed from ACU.
If the resistance is OK, the inlet thermistor
is good. Proceed to step 4.
If the thermistor resistance does not agree
with the table, replace the inlet thermistor.
TEMP.
°F (°C)
RES.
RANGE
k ohms
TEMP.
°F (°C)
RES.
RANGE
k ohms
68°
(20°)
61.2–63.7
131°
(55°)
14.5–15.3
77°
(25°)
49.0–51.0
140°
(60°)
12.1–12.8
86°
(30°)
39.5–41.1
149°
(65°)
10.2–10.7
95°
(35°)
32.0–33.3
158°
(70°)
8.5–9.0
104°
(40°)
26.1–27.2
167°
(75°)
7.2–7.6
113°
(45°)
21.4–22.3
176°
(80°)
6.1–6.5
122°
(50°)
17.6–18.5
ELECT - INLET THERMISTOR RESISTANCE
TEMP.
°F (°C)
RES.
RANGE
k ohms
TEMP.
°F (°C)
RES.
RANGE
k ohms
68°
(20°)
57.5–67.6
131°
(55°)
14.1–15.6
77°
(25°)
46.1–53.8
140°
(60°)
11.8–12.9
86°
(30°)
37.4–43.1
149°
(65°)
9.9–10.8
95°
(35°)
30.4–34.7
158°
(70°)
8.4–9.0
104°
(40°)
24.9–28.2
167°
(75°)
7.1–7.6
113°
(45°)
20.5–23.0
176°
(80°)
6.0–6.4
122°
(50°)
16.9–18.9
GAS - INLET THERMISTOR RESISTANCE