Pipe Sizing For Gas Connections

Page 20 highlights

GAS PRESSURE REGULATOR The gas pressure regulator is preset at 4.0 in. WC for natural gas (3.1 in. WC for Lo NOx), and 10.5 in. WC. for propane gas. The pressure at the gas valve, taken with a manometer, should be about 4.0 in. WC natural gas (3.1 in. WC for Lo NOx) and 10.5 in. WC propane gas. If an adjustment is needed, remove seal and turn adjustment screw clockwise to increase pres- sure or counter-clockwise to decrease pressure. NOTE: Lo NOx gas valves are non-adjustable; settings are fixed by the manufacturer (Invensys/Robertshaw). ELECTRONIC IGNITION GAS VALVES-CONTINUED Gas Pressure Adjustment Robertshaw 7200 (Heater Model 206) Robertshaw 7000 BDER (Heater Models 266-336) MANUAL SHUT-OFF VALVE UNION Gas Pressure Adjustment Robertshaw 7000 DERHC (Heater Model 406) Non-Adjustable Gas Valve MANOMETER GAS PRESSURE TEST AT GAS VALVE GAS PRESSURE ADJUSTMENT LOCATIONS MILLIVOLT GAS VALVES Robertshaw 7000 BDERF (Heater Models 207-407) PIPE SIZING FOR GAS CONNECTIONS Gas Pressure Adjustment Robertshaw 7000 (Heater Models 206-406) ELECTRONIC IGNITION GAS VALVES Gas Pressure Adjustment Honeywell VR8304 (Heater Models 206406 and 207-407) Maximum Equivalent Pipe Length (ft) Natural Gas 1000 BTU/FT3 0.60 Specific Gravity @ 0.5 in. WC Pressure Drop Propane Gas 2500 BTU/FT3 1.53 Specific Gravity @ 0.5 in. WC Pressure Drop Input 3/4" 1" 1-1/4" 1-1/2" Model (KBTU) N P N P N P N P 206/207 199.5 25 60 90 215 360 266/267 266.0 15 35 50 125 210 480 445 336/337 332.5 10 20 30 80 140 320 290 406/407 399.0 * 15 20 55 95 225 215 480 *A 3/4" gas line can be used for up to 5 ft maximum length from the gas valve in addition to the sediment trap. 20

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56

GAS PRESSURE REGULATOR
The gas pressure regulator is preset at 4.0 in. WC for
natural gas (3.1 in. WC for Lo NOx), and 10.5 in. WC.
for propane gas. The pressure at the gas valve, taken
with a manometer, should be about 4.0 in. WC natural
gas (3.1 in. WC for Lo NOx) and 10.5 in. WC propane
gas. If an adjustment is needed, remove seal and turn
adjustment screw clockwise to increase pres-
sure or counter-clockwise to decrease pressure.
NOTE:
Lo NOx gas valves are non-adjustable; set-
tings are fixed by the manufacturer
(Invensys/Robertshaw).
20
GAS PRESSURE ADJUSTMENT LOCATIONS
MILLIVOLT GAS VALVES
ELECTRONIC IGNITION GAS VALVES
Gas Pressure
Adjustment
Gas Pressure
Adjustment
Robertshaw 7000
(Heater Models 206-406)
Honeywell VR8304
(Heater Models 206-
406 and 207-407)
ELECTRONIC IGNITION GAS VALVES-CONTINUED
Gas Pressure
Adjustment
Robertshaw 7200
(Heater Model 206)
Robertshaw 7000 BDER
(Heater Models 266-336)
Gas Pressure
Adjustment
Robertshaw 7000 DERHC
(Heater Model 406)
PIPE SIZING FOR GAS CONNECTIONS
Robertshaw 7000 BDERF
(Heater Models 207-407)
Non-Adjustable
Gas Valve
Maximum Equivalent Pipe Length (ft)
Natural Gas 1000 BTU/FT
3
0.60
Specific Gravity @ 0.5 in. WC Pressure Drop
Propane Gas 2500 BTU/FT
3
1.53
Specific Gravity @ 0.5 in. WC Pressure Drop
Input
3/4”
1”
1-1/4”
1-1/2”
Model
(KBTU)
N
P
N
P
N
P
N
P
206/207
199.5
25
60
90
215
360
266/267
266.0
15
35
50
125
210
480
445
336/337
332.5
10
20
30
80
140
320
290
406/407
399.0
*
15
20
55
95
225
215
480
MANUAL
SHUT-OFF
VALVE
UNION
MANOMETER
GAS PRESSURE TEST
AT GAS VALVE
*A 3/4” gas line can be used for up to 5 ft maximum length from the
gas valve in addition to the sediment trap.