Tripp Lite 9PX6KL Eaton 9PX 6KVA Lithium-Ion Advanced Users Guide 9PX6K-L 9PXE - Page 25
Power Cables Connection
View all Tripp Lite 9PX6KL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Power Cables Connection 3.8 Power Cables Connection Access to Terminal Blocks 1. Remove the terminal blocks cover (one screw) 2. Punch the knockouts and insert the cables/conduits inside High leakage current. Earth connection essential before connecting supply. NOTE The L6-30P input power cable is attached by Eaton. NORMAL AC SOURCE N(L2) L1 This type of connection must be carried out by qualified electrical personnel. Before carrying out any connection, check that the upstream protection device (Normal AC source) is open "O" (Off). Always connect the ground wire first If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the terminal blocks connection of the UPS with this accessory. 1 Insert the Normal AC cable through the cable gland. 2 Connect the three cables to the Normal AC source terminal blocks. 3 Insert the Output cable through the cable gland. 4 Connect the three cables to the Output terminal blocks. 5 Put back and secure the terminal blocks cover with the screw. 6 Tighten the cable glands. 3.9 Detecting Other Accessories Tip If you ordered other UPS accessories, refer to specific user manuals to check the connection to the UPS. OUTPUT N(L2) L1 Eaton 9PX Lithium-Ion User Guide DPD-9PX2206-Rev 01 19